Bindicator TDR-3000 Installation & Operation Manual page 25

Two-wire guided wave radar
Table of Contents

Advertisement

Name (number), function
Emptying speed (P27)
Current loop output (P12a),
Value of output current if there is an
error (error current)
Value assigned to 4 mA
(P10)
Value assigned to 20 mA (P11)
HART® short address (P19),
Device address
TDR180003 Rev. I
Adjustable value range
Default value
0.1...900 m/h (0.33...2950 ft/h)
200 m/h (656 ft)
Selectable values:
− Hold
− 3.8 mA
− 22 mA
Hold
Selectable values:
In accordance with the PV
adjustment range, usually minimum
value
0.000 m (0.000 ft)
Selectable values:
In accordance with the PV
adjustment range, usually maximum
value
0...15
0
21
www.bindicator.com
Description
The maximum rate of dropping in
the tank during emptying. Entering
it correctly makes the measurement
more reliable during emptying.
SAP–300: no adjustment available
This parameter determines the state
that the current loop output draws
in the event of a fault. For "Hold," it
keeps the last measured value (4...
20 mA), for "3.8 mA" and "22 mA"
it keeps the indicated value until the
fault is present.
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / ERROR MODE
PV value assigned to 4 mA in current
transmission mode (usually the lower
limit of the measuring range for level
measurement).
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / 4mA VALUE
PV value assigned to 20 mA in
current transmission mode (usually
the upper limit of the measuring
range for level measurement).
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / 22mA VALUE
Unique device address based on
which the device can be identified
and managed via the HART® BUS.
• 0: analog output active (current
loop transmission active, 4...20 mA)
• 1...15: analog output inactive (no
current loop transmission, constant 4
mA), Multidrop
Display:
MAIN MENU / OUTPUT SETUP /
SERIAL OUTPUT / ADDRESS