Name (number), function
Emptying speed (P27)
Current loop output (P12a),
Value of output current if there is an
error (error current)
Value assigned to 4 mA
(P10)
Value assigned to 20 mA (P11)
HART® short address (P19),
Device address
TDR180003 Rev. I
Adjustable value range
Default value
0.1...900 m/h (0.33...2950 ft/h)
200 m/h (656 ft)
Selectable values:
− Hold
− 3.8 mA
− 22 mA
Hold
Selectable values:
In accordance with the PV
adjustment range, usually minimum
value
0.000 m (0.000 ft)
Selectable values:
In accordance with the PV
adjustment range, usually maximum
value
0...15
0
21
www.bindicator.com
Description
The maximum rate of dropping in
the tank during emptying. Entering
it correctly makes the measurement
more reliable during emptying.
SAP–300: no adjustment available
This parameter determines the state
that the current loop output draws
in the event of a fault. For "Hold," it
keeps the last measured value (4...
20 mA), for "3.8 mA" and "22 mA"
it keeps the indicated value until the
fault is present.
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / ERROR MODE
PV value assigned to 4 mA in current
transmission mode (usually the lower
limit of the measuring range for level
measurement).
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / 4mA VALUE
PV value assigned to 20 mA in
current transmission mode (usually
the upper limit of the measuring
range for level measurement).
Display:
MAIN MENU / OUTPUT SETUP /
ANALOG OUTPUT / 22mA VALUE
Unique device address based on
which the device can be identified
and managed via the HART® BUS.
• 0: analog output active (current
loop transmission active, 4...20 mA)
• 1...15: analog output inactive (no
current loop transmission, constant 4
mA), Multidrop
Display:
MAIN MENU / OUTPUT SETUP /
SERIAL OUTPUT / ADDRESS