The Behavior of the TDR while Programmed Manually
By default, the TDR displays the main measurement data on the display (hereafter referred to as display).
Enter the programming menu by pressing the E button. Use the / buttons to navigate through the menu items.
Enter the selected menu item with the E button. Return to the previous menu level with the key.
The buttons only work if the display is present!
The device continues measuring while the menu is accessed. Changes made in the menu take effect when you exit
the menu.
If you do not exit the TDR menu, the device will automatically return to the measurement display state after 30
minutes. In this case, any changes made in the menu will be ignored.
If the display is pulled out of the TDR, the TDR will automatically exit the menu and ignore any changes made in the
menu.
Manual Programming
Press the E button to modify the parameter under the cursor in the submenu.
There are two modes:
Text list: Navigated is same as in the menu. The E button executes the selection, and the button cancels it.
Editable number field: Serves to edit numeric values. Editing is aided by an (inverted) cursor. The number under
the cursor can be changed with the / buttons (no overflow). The cursor can be moved left with the arrow (max.
9 character-positions, including the decimal point). When the end of the field is reached, the cursor returns to
the first position on the right. Editing is concluded by pressing the E button. In this case, display will check the
entered value and if it is not correct, "WRONG VALUE!" is displayed in the bottom row.
WARNING: All TDR-3000s are built to the specifications provided by the user. Any modifications made without
Anderson-Negele may result in a voided warranty.