Bindicator TDR-3000 Installation & Operation Manual page 22

Two-wire guided wave radar
Table of Contents

Advertisement

Name (number), function
Maximum measurement range limit
(P06),
Remote blocking
Damping time (P20)
Time constant
Probe length (P03)
Fixed output current (P08),
Setting constant output current
System of measurement units, units
of measurement:
Adjustable value range
Default value
0 (limiter off) or the minimum
measuring distance. The distance
between (P05) +5 cm and the probe
length (P03)
0
(off)
0...999 sec
10 sec
0.1...30 m
(0.33...100 ft)
This distance plus an additional
0.66 ft (0.2 m). It is the hard limit of
the measurement. (Excess is used
up for probe end detection and
pollution of the probe.)
3.8...22 mA
4
18
www.bindicator.com
Description
The maximum value of the
measuring range of the device
can be limited with this parameter.
Signals received beyond the set
distance will not be processed. Its
value is calculated from the plane
of the lower sealing surface of the
mechanical connector (in the case
of a flanged version, from the lower
plane of the flange).
Remote blocking can be turned off
by setting the parameter to 0. In
this case, the device will give a valid
result along the entire length of the
sensor.
MAIN MENU / MEASUREMENT
CONFIG / MAX. MEAS. DIST.
The "Damping time" is used to
reduce undesired fluctuations
(e.g.: rippling) in the display of the
measured data. If the level changes
abruptly, the new value will be set
to within 1% accuracy (exponential
setting). Unit of measure: seconds.
MAIN MENU / MEAS.
OPTIMIZATION / DAMPING TIME
When the current output is set
to "Fixed" mode (P12b = 1), the
constant current set here is set.
The PV current transmission does
not work, and at the same time, it
overrides any current output fault
indication.
MAIN MENU / OUTPUT SETUP
/ ANALOG OUTPUT / MANUAL
VALUE
When the current output is set
to "Fixed" mode (P12b = 1), the
constant current set here is set.
The PV current transmission does
not work, and at the same time, it
overrides any current output fault
indication.
MAIN MENU / OUTPUT SETUP
/ ANALOG OUTPUT / MANUAL
VALUE
Path of parameters: "Settings" /
Application" tab
TDR180003 Rev. I