Bindicator TDR-3000 Installation & Operation Manual page 21

Two-wire guided wave radar
Table of Contents

Advertisement

PROGRAMMING
− Programming with the display unit
Name (number), function
Zero-level distance (P04),
Set container height
Minimum measuring distance (P05),
Signal echoes found within the dead
zone are not processed.
Warning!
Critical parameter!
Tank full limit (P29)
TDR180003 Rev. I
Adjustable value range
Default value
0...60 m
(0...200 ft)
As per order
Minimum measuring distance...
probe length (P03)
"Minimum measuring distance"
according to the Probe data table
Limits are 0 to Probe length (P03).
Factory value minimum
measurement distance according to
the probe type.
17
www.bindicator.com
Description
It provides the basis for level
measurement calculations. The
distance between the plane of
the lower sealing surface of the
mechanical connector (the lower
plane of the flange in the case of a
flanged version) and the reference
point at the bottom of the tank. Its
value must be set in a distance unit
(Unit - P00b).
Note: If measured distance is
between this distance and dead
zone, then this distance will be held.
MAIN MENU / CALCULATION /
ZERO-LEVEL DISTANCE
The dead zone is the distance
between the plane of the lower
sealing surface of the mechanical
connection (the lower plane of the
flange in the case of the flanged
version) and the highest level in the
tank. Signals generated within the
dead zone are not processed. The
current loop output does not follow
the dead zone level signal. Its value
must be set in distance units (Length
unit – P00b).
Note: If the measurement exceeds
this distance then this distance will
be held.
MAIN MENU / MEASURETMENT
CONFIG / MIN. MEAS. DIST.
Echoes between this and P05
are processed. However if the
measurement distance is in this
range then the "Tank full limit
distance" is returned or used up for
calculations.