Safety; Connection Technology; Table 7 Technical Data - Signal Output; Table 8 Technical Data - Safety - WAGO 787-3861/108-020 Manual

Electronic circuit breaker
Table of Contents

Advertisement

787-3861/108-020
Property
Series circuit
1)
The power supply must be able to deliver the maximum required power without the voltage falling below
20 VDC.
2)
Verified connectable load capacities depend on the power supply used; see
Property
Signal output
See also
2 Power Supplies [} 38]

3.5.4 Safety

Property
Rated voltage
Protection type
Insulation coordination UL
Overvoltage category
Pollution degree
Type pf insulation
Dielectric strength
Insulation coordination
Overvoltage category
Pollution degree
Type pf insulation
Dielectric strength
1)
Between adjacent products of the same type.

3.5.5 Connection Technology

Parameters
Connection Technology
Solid "s"
Fine-stranded "f"
Strip length
1)
The conductor temperature can be up to 90 °C. Use only conductors that can withstand the anticipated tem-
perature.
Product manual | Version: 1.0.0
Electronic Circuit Breaker
Voltage Level
Value
Non-isolated 24 VDC output, short-circuit-protected, can be commoned
across max. 10 devices (relative to the device GND input)
High level
18 ... 30 V at maximum current load 15 mA
1)
1)
1)
1)
Value
Prohibited
8 Power Supplies [ }
Table 7: Technical Data – Signal Output
Table 8: Technical Data – Safety
Value
300 V
IP20
II
2
Functional insulation
1.5 kVDC (1 min.)
II
2
Reinforced insulation (safe isolation)
3 kVDC (1 min.)
Table 9: Technical Data – Connection Technology
Value
®
Push-in CAGE CLAMP
0.08 ... 2.5 mm² / 28 ... 14 AWG
0.34 ... 2.5 mm² / 22 ... 14 AWG
9 mm ... 10 mm / 0.37 in
Properties
 38].
15

Advertisement

Table of Contents
loading

Table of Contents