Distributing And Multiplying A Potential; Commoning; Potential Distribution Module; Channel Lock - WAGO 787-3861/108-020 Manual

Electronic circuit breaker
Table of Contents

Advertisement

Functions

4.6 Distributing and Multiplying a Potential

The product has two connection points for the positive output (connections 6 and 7) and
two connection points for the negative input/output (connections 4 and 8).
Once the device is powered by a push-in type jumper bar, two load circuits can be con-
nected directly to the device (V
Observe the following note if you would like to common potentials with relays:
NOTICE
!
Connected relays: Only common equal potentials!
Damage to the device may occur if different potentials are commoned!
If you use the relay with item no. 857-304, the potentials must only be commoned via
connections V
You can find a connection example in

4.6.1 Commoning

Push-in type jumper bars can be used to distribute an applied voltage or signal to multiple
electronic circuit breakers.
• Commoning the power supply:
The maximum supply current per connection point is 20 A. A current of 40 A can be
distributed across multiple ECBs if the potential is fed in and commoned in parallel via
two connection points.
• Commoning signal output S2:
The signal outputs of up to 10 devices can be commoned and then serve as a common
signal.
The respective products can be found as "related products" under
787-3861/108-020.

4.6.2 Potential Distribution Module

WAGO's Power Distribution Modules (PDM) allow parallel connection with multiple lines
to the fused supply voltage and GND potential by expanding product connections V
GND
The housing contours and dimensions are based on the electronic circuit breakers. This
allows the connection from PDM to push-in type jumper bars to be made directly; see
8 Commoning
also
under ü www.wago.com/787-3861/108-020.

4.7 Channel lock

The current dial can be used to set the channel lock. This setting switches off the output
of the product and the LED lights up red (see Sprungziel: Zustände, "Status 7").
In this state, the output cannot be switched on manually with a button or via the control in-
put.
26
Product manual | Version: 1.0.0
Electronic Circuit Breaker
+ (connection 3) and GND (connection 8)!
IN
(8 Connections
[} 12]).
[} 26]. The respective products can be found as "related products"
+/GND). Additional terminal blocks can be omitted.
OUT
8 Connection Examples
787-3861/108-020
[} 28].
ü www.wago.com/
or
out+

Advertisement

Table of Contents
loading

Table of Contents