3.5.6 Environmental Requirements

Note
At nominal current ≤ 4 A there is no ambient temperature restriction!
For products with nominal current ≤ 4 A , there is no restriction of the ambient tempera-
ture range in the form of derating. The devices in the specified range −25 ... +70 °C can
be fully used.
Restrictions in the form of derating must be taken into account in accordance with
the following tables for nominal current of 4 A or more.
Parameter
Ambient temperature, operation
Ambient temperature, storage
Relative humidity
Elevation above sea level
Mounting Posi-
tion in Control
Cabinet
Stand-alone
Arranged in series
(series of 5
Mounting Position horizontal
Horizontal stand-alone
Horizontal (series of 3
Horizontal (series of 5
Horizontal (series of 9
Horizontal (series of 13
Horizontal (series of 15
1)
Series: Same devices with the same load.
2)
Determined by simulation.

3.6 Guidelines, approvals and standards

3.6.1 Regulations and Standards

Name
EU EMV Directive
Safety requirements for electrical equipment for mea-
surement, control, and laboratory use
Part 2-201: Particular requirements for control equip-
ment
16
Product manual | Version: 1.0.0
Electronic Circuit Breaker
Table 11: Technical Data – Mounting Positions and Ambient Temperatures in the Control Cabinet
0.5 ... 4 A
−25 ... +70 °C
−25 ... +70 °C
1)
)
Table 12: Technical Data – Horizontal Mounting Positions and Ambient Temperatures
1)
)
1)
)
1)
)
1)
)
1)
)
Table 10: Technical Data – Environmental Conditions
Value
−25 ... +70 °C
−40 °C ... +85 °C
10 ... 95 %  (no condensation permissible)
2000 m
Ambient Temperatures
5 ... 6 A
−25 ... +70 °C
−25 ... +60 °C
Ambient Temperatures 7 ... 8 A
−25 ... +70 °C
−25 ... +40 °C
−25 ... +35 °C
−25 ... +15 °C
−25 ... +10 °C
−25 ... +5 °C
Table 13: Standards and Regulations
Standard
2014/30/EU
EN 61010-2-201
787-3861/108-020
7 ... 8 A
−25 ... +70 °C
−25 ... +35 °C
2)