Diagnostics; Diagnostics Via Indicators; Table 19 General Operating Statuses - WAGO 787-3861/108-020 Manual

Electronic circuit breaker
Table of Contents

Advertisement

Diagnostics

8 Diagnostics

8.1 Diagnostics via Indicators

Operating Status 
Status 0:
Initialization of the product (boot process).
Status 1:
Channel switched on.
Status 2:
Channel switched on.
Load current > 90 % of nominal current
Status 3:
Channel switched on.
Load current > 100 % nominal current
Status 4:
Channel switched off manually or by control
input S1.
Status 5:
Channel tripped.
Wait for temperature to return to normal.
Status 6:
Channel tripped.
Temperature has returned to normal.
Channel can be switched back on.
Status 8:
Channel tripped.
Undervoltage
Status 9:
Channel tripped.
Overvoltage
Status 10:
Product error, wiring error, feedback voltage
1 This status may differ after configuration. More information can be found in table "Signal Output S2 – Signal-
ing" (see
2 The channel is switched back on with a time delay (0 ... 500 ms).
3 The channel is automatically switched off according to the tripping characteristic given. The product then
switches to status 5.
4 The status is saved when the input voltage is switched off.
5 After a waiting time (temperature returns to normal), the channel switches to status 6.
6 The channel can be switched back on as follows:
- Pushing the button twice, or
- Applying a pulse (signal 1) to the control input (see
The product then switches to status 1.
34
Product manual | Version: 1.0.0
Electronic Circuit Breaker
3
4
6
8 Control Input S1 and Signal Output S2 [ }
LED State
Level At Sig-
nal Output S2
Off
0 V
2
Green
24 V
Green, flashing
24 V
(1 Hz)
Green, flashing
24 V
(5 Hz)
Red
24 V
Red, flashing
0 V
(1 Hz)
5
Flashing yellow 0 V
Red/yellow,
0 V
flashing
(1 Hz)
Red/yellow,
0 V
flashing
(5 Hz)
Red/yellow/
0 V
green
One after the
other
(1 Hz)
 24]).
8 Control Input S1 and Signal Output S2 [ }
787-3861/108-020
Table 19: General Operating Statuses
Button
Signal at Con-
1
Pushed
trol Input S1
Status 4
Signal 3 →
Status 4
Status 4
Signal 3 →
Status 4
Status 4
Signal 3 →
Status 4
Status 1
Signal 2 →
Status 1
Status 4
Signal 1 →
Status 1
 24]).

Advertisement

Table of Contents
loading