transmitter: -40℃~+70℃
The ambient temperature for intrinsically safe transmitter: -20
℃~+70℃ (with LCD display)
*The ambient temperature for intrinsically safe transmitters
should adhere to the group specified in the local area
certification certificate.
Storage temperature:-40℃~+100℃ (Silicone oil)
-40℃~+160℃ (Inert oil)
0℃~+315℃ (High temperature silicone oil)
(7) Applicable humidity
5%RH ~ 100%RH@40℃ (depending on whether the wiring
cavity and cables are sealed or not)
(8) Overpressure and static pressure limit
Differential pressure transmitter overpressure: 25MPa
Static pressure:16MPa ( -40℃~85℃) , 42MPa ( -20℃~85℃)
(9) Fault alarm
When a fault occurs in transmitter component, the
self-diagnosis program drives the output of a warning
message or a settable alarm current according to the user's
selection.
(10) Configuration
Configuration can be realized through button settings or
HART protocol digital communication.
(11) Damping settings
0~100 seconds (set via communication or transmitter).
(12) Explosion-proof certificate
China's explosion-proof mark and performance
43