7 Accessories

Description
E+E Product Configuration Software
(Free download from www.epluse.com/pcs10)
USB Configuration Adapter for TES201 digital

8 Technical Data

Measurands
Temperature (T)
Measuring range
1)
Accuracy
Temperature dependency of electronics, typ.
Factory calibration uncertainty
@ 23 °c (73 °F)
1) Defined @ 23 °C (73 °F) against E+E calibration reference. With supply voltage 24 V DC, 0.2 m/s (39. 4 ft/min) medium flow and load
resistor 250 Ω for version with current output.
2) Defined with an enhancement factor k=2, corresponding to a confidence level of 95 %.
Outputs
Analogue
T: acc. to ordering guide
Digital
Digital interface
Protocol
Factory settings
Supported Baud rates
Measured data type
Protocol
Factory settings
Supported Baud rates
1) Ex works: see ordering guide.
Code
PCS10
HA011066
-30...+60 °C (-22...+140 °F)
0- 10 V, RS485
±0.25 °C (±0.14 °F)
4 - 20 mA
±0.38 °C (±0.21 °F)
0.006 K/K
2)
±0.1 °C (±0.056 °F)
0 - 10 V
4 - 20 mA (2-wire)
RS485 (TES201 = 1 unit load)
Modbus RTU
Baud rate see ordering guide, parity even, 1 stop bit, Modbus address 45
1)
9 600, 19 200 and 38 400
FLOAT32 and INT16
BACnet MS/TP
BACnet address 45
1)
9 600, 19 200, 38 400, 57 600, 76 800 and 115 200
User Manual TES201
-1 mA < I
< 1 mA
L
R
< 500 Ω
L
Room Sensor for Temperature | 19
I
= load current
L
R
= load resistance
L