8.2 List of I/O Allocations

8.2 List of I/O Allocations

Input contact
Address
CH0
CH1
X0
X1
X2
X3 to
XF
Output contact
Address
CH0
CH1
Y0 to
YF
Y10
Y11 to
Y1F
(Note 1)
The I/O numbers in the tables above show offset addresses. I/O numbers actually allocated are based
on the first word number allocated to the unit. Example) If the first word number is "10", the D/A
conversion data on CH0 and the error flag will be WY10 and X100, respectively.
8-4
CH2
X10
X20
X11
X21
X12
X22
X13 to
X23 to
X1F
X2F
CH2
Y20 to
Y40 to
Y2F
Y4F
Y30
Y50
Y31 to
Y51 to
Y3F
Y5F
Name
CH3
X30
Error flag
Upper limit of
X31
upper and lower
output clipping
Lower limit of
X32
upper and lower
output clipping
X33 to
Not used
X3F
Name
CH3
D/A conversion
Y60 to
data
Y6F
(16 bit)
Upper and lower
limit output
Y70
clipping function
execution relay
Y71 to
Not used
Y7F
Description
Turns ON when an error is
detected.
Turns ON when the output exceeds
the upper limit of output clipping,
provided that the upper and lower
limit function is active.
Turns ON when the output drops
below the lower limit of output
clipping, provided that the upper
and lower limit function is active.
Do not use.
Description
Set a digital value corresponding to
the analog output.
<Voltage range>
-10 to +10 V: -31,250 to +31,250
0 to +10 V or 0 to +5 V: 0 to
+31,250
+1 to +5 V: 0 to +25,000
<Current range>
+0 to +20 mA: 0 to +31,250
+4 to +20 mA: 0 to +25,000
* Apply a digital value within the set
scale if scale conversion is set.
The upper and lower output limit
clipping function is executed with
the relay turned ON.
With the relay turned OFF,
the upper limit flag (Xn1) for upper
and lower output clipping limits
and the lower limit flag (Xn2) for
upper and lower output clipping
limits are turned OFF.
Do not use.
WUME-FP7AOH-03