Settings; Unit Setting And Conversion Processing Time - Panasonic AFP7DA4H User Manual

Fp7 analog output unit
Hide thumbs Also See for AFP7DA4H:
Table of Contents

Advertisement

4.2 Configuration Settings
The set value will become effective when the set value is downloaded together with a
corresponding program as a project.

4.2.3 Settings

Group
Basic setting
items
(per channel)
Option setting
items
(per channel)

4.2.4 Unit Setting and Conversion Processing Time

Conversion time varies with the configuration setting conditions.
Conversion processing execution / non-execution setting and conversion
processing time
Select the execution or non-execution of the conversion processing of analog output on a
channel-by-channel basis. This can save the conversion time for channels that do not execute
conversion processing. A conversion time of 25 μs is required per channel.
Example) Conversion time for four channels
4-6
Setting item
Output processing
Range setting
Upper and lower output clipping
Upper limit
Lower limit
Scale conversion
Max. value
Min. value
Offset / Gain processing
Offset value
Gain value
Analog output in PROG. mode
A digital value
corresponding to
the desired
analog output

Settings

Execute / Not execute
-10 V to +10 V
0 V to +10 V
0 V to 5 V
+1 V to 5 V
0 V to 20 mA
4 mA to 20 mA
Execute / Not execute
-32,500 to +32,500
-32,500 to +32,500
Execute / Not execute
-30,000 to +30,000
-30,000 to +30,000
Execute / Not execute
-3,000 to +3,000
+9,000 to +11,000
Non-hold / Current value hold /
Desired value hold
-32,500 to
-10 to +10 V
+32,500
0 to +10 V
0 to 5 V
0 to +32,500
0 to 20 mA
+1 to 5 V
0 to +25,000
4 to 20 mA
Default
Execute
-10V to +10 V
Not execute
0
0
Not execute
10000
0
Not execute
0
10000
Non-hold
0
WUME-FP7AOH-03

Advertisement

Table of Contents
loading