6.4 Analog Output Hold while in PROG. Mode

Overview of functions
This function holds analog output when the PLC mode is switched from RUN to PROG.
● Make analog output hold settings on a channel-by-channel basis.
● The analog output value can be set to "Desired value hold", "Current value hold" or "Non-
hold" on a channel-by-channel basis.
(Note) The converted digital value varies with the setting of the range if "Desired value hold"
is set.
Configuration
Name
Function setting
Analog output in
PROG. mode
Analog output in PROG. mode
(Note 1)
This configuration is enabled when "Analog output hold settings while in PROG. Mode" is set to
"Desired value hold".
● If no analog output is held, the output will be turned OFF (0 V or 0 mA) while in PROG. mode.
● The output will be turned OFF (0 V or 0 mA) if an error occurs.
WUME-FP7AOH-03

6.4 Analog Output Hold while in PROG. Mode

Default
Setting range and description
Non-
Non-hold / Current value hold / Desired value hold
hold
K0
Set a digital value corresponding to the analog output when
(Note 1)
a desired value is set for the analog output while in PROG.
mode.
Setting range: -31,250 to +31,250 (Specified with a signed
integer)
6-7