Current Range; Current Output Range: 0 To +20 Ma (0.64 Μa, 1/31,250); Current Output Range: +4 To +20 Ma (0.64 Μa, 1/25,000) - Panasonic AFP7DA4H User Manual

Fp7 analog output unit
Hide thumbs Also See for AFP7DA4H:
Table of Contents

Advertisement

5.2 Current Range

5.2.1 Current Output Range: 0 to +20 mA (0.64 μA, 1/31,250)
5.2.2 Current Output Range: +4 to +20 mA (0.64 μA, 1/25,000)
WUME-FP7AOH-03

5.2 Current Range

Output range: 0 to +20 mA
Digital input
Analog output
value (K)
value (V)
+31,250
+20
+25,000
+16
+18,750
+12
+12,500
+8
+6,250
+4
0
0
When exceeding the rated
range
Digital input
Analog output
value
value
+32,500 or
Output at +
more
20.8 mA
-1,250 or less
Output at -0.8
mA
Output range: 0 to +20 mA
Digital input
Analog output
value (K)
value (V)
+25,000
+20
+18,750
+16
+12,500
+12
+6,250
+8
0
+4
When exceeding the rated
range
Digital input
Analog output
value
value
+26,250 or
Output at +
more
20.8 mA
-1,250 or less
Output at +3.2
mA
5-5