4.1 Confirming the I/O Number Allocations and First Word Number
Address
CH0
CH1
Y11 to
Y1F
(Note 1)
The I/O numbers in the tables above show offset addresses. I/O numbers actually allocated are based
on the first word number allocated to the unit. Example) If the first word number is "10", the D/A
conversion data on CH0 and the error flag will be WY10 and X100, respectively.

4.1.2 Confirming the I/O Number Allocations

● I/O numbers and base word numbers are always necessary when writing programs. Always
check to see if the numbers match the design.
● I/O numbers allocated are determined by the first word number.

4.1.3 Allocations to unit

Take the following procedure to set the first word number.
1.
Select Options>FP7 Configuration from the menu bar.
2.
Select "I/O Map" from the field.
3.
Double-click the target slot where the operating unit is to be inserted.
4.
Select "Analog I/O" and "Output Unit"in the unit selection field.
WUME-FP7AOH-03
CH2
Y31 to
Y51 to
Y3F
Y5F
Name
CH3
Y71 to
Not used
Y7F
Description
Do not use.
4-3