Configuration By Programming - Panasonic AFP7DA4H User Manual

Fp7 analog output unit
Hide thumbs Also See for AFP7DA4H:
Table of Contents

Advertisement

6.5 Configuration by Programming

6.5 Configuration by Programming

Overview of functions
● The FP7 analog output unit makes it possible to overwrite the configuration information by
programming.
● The configuration information is refreshed by writing "55AA" to unit memory UM 00028 after
the value is stored in the unit memory where a desired parameter is set.
● The value of unit memory UM 00028 will be set to "0" when the configuration information is
updated.
Sample program
Output processing: CH0 and CH1 are executed and CH2 and CH3 are non-executed for the
implementation output range of 0 to +20 mA.
R0
(
)
DF
6-8
MV.US
H0001
MV.US
H0001
MV.US
H0010
MV.US
H0010
MV.US
H0000
MV.US
H0000
MV.US
H55AA
S1: UM00108
Output processing:
Execute
S1: UM00118
S1: UM00109
Output range:
Set CH0 to CH1 to 0
to +20 mA
S1: UM00108
S1: UM00139
Setting CH2 and CH3
to non-execute
S1: UM00151
S1:UM00028
Setting updating
WUME-FP7AOH-03

Advertisement

Table of Contents
loading