The user can confirm the modification of the calibration interval by pressing ENTER. The
user can cancel the modification and return to the info menu by pressing ESC.
5.4.2 Renewing the validity of the calibration
Usually, the validity of the calibration settings for the detector is renewed automatically when
it is calibrated by a technician certified by DALEMANS sa/nv. The maintenance interval for
the calibrated detector is then reset.
In some specific cases, the detector may need to be verified by a certified control authority
and the validity of the calibration of this detector may then be extended.
The detector is displayed with the number of days that have lapsed since its last calibration
and the full-scale value of the gas concentration that the detector is able to estimate.
Detector 1
346 days
The user can confirm their selection of detector by pressing ENTER. The system then asks
the user to confirm the renewal of the validity of the calibration for the selected detector.
Detector 1
Renew calibration?
The user can confirm the renewal of the validity of the calibration for the detector by
pressing ENTER. The next maintenance date may have been modified at this point. The
user can cancel the modification and return to the info menu by pressing ESC.