4.3.8 Errors reset mode
The U•H1 Control Unit has an internal fault management. Once detected, any abnormal
operation of the U•H1 Control Unit or detector is notified by an action on the relay indicating
a technical fault.
The mode to reset a technical fault specifies how it is reset:
Automatic reset:
When the cause of the error restored, the message is automatically reset and disappears.
Manual reset:
When the cause of the error disappears, the message remains visible until the user manually
acknowledges it by pressing twice on the MUTE/RESET button.
Changing the error reset mode should be conducted by a technician certified by
DALEMANS sa/nv.
4.4 Status menu
The Status menu allows the user to view the status of the components of the U•H1 unit.

Measurement info

Outputs

Power supply
[Value]
xxxx

Temperature
[xx °C]
xx °C
DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
Error reset mode
Automatic
Error reset mode
Manual acknowledge
Sub-menu
Measurement
Channels
Outputs
Power Supply
Temperature
U•H1 Instruction Manual
Provides the status:
-
Disabled: the system
considers this channel to be
inactive
-
Measurement Display
Provides the status of the outputs:
-
The system considers this
output to be disabled.
-
enabled/disabled
The voltage of the unit is displayed.
Indicates the temperature of the U•H1
unit: pressing ENTER causes the
system to display the minimum,
average and maximum temperatures.