For single phase models (VE05-1P and VE09-
1P) the system will give the option to select the
voltage to match the incoming electrical supply
(either 200V or 230V). Note that 230V is the UK
standard.
• Touch either 200 or 230V
• Touch the tick to save the required selection
C
This screen allows the type of control for the
humidifier to be set. There are 5 different
options available as discussed on page 8
previously. One of the options must be selected
and a corresponding input must be provided for
the unit to operate.

Cylinder selection

The chart below details how to select the correct cylinder for the model of unit and the water
conductivity range. Scotland is a typical "soft water" area; the midlands is a typical "normal water
hardness" area; and London is a typical "hard water" area.
For cylinder type L, N or H refer to the water conductivity and unit type to select recommended cylinder
Cylinder
Voltage Band
200
1 PH & N
400
2/3 PH
400
3 PH
Unit Type
VE 05-1P
VE 09-1P
VE 09-3P
VE 18-3P
VE 30-3P,
VE 45-3P,
NOTE:
Page No 34 of 80
Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0
Vapac Cylinder Selection for the standard VE Virtuoso Range
Cylinder Rating and Water Conductivity micro Siemens per cm
80
100
200
300
L
L
N
L
80
100
200
300
VE60-3P (Two Cylinders).
VE 90-3P (Two Cylinders)
Stainless steel versions available on request
The above is to be taken as a guide only. In exceptional circumstances alternatives may be required.
Once the input type has been selected, the unit
will enter the Normal Operating Mode

Critical Alarm

A CRITICAL ALARM is raised if the current
consumption increases above a preset
maximum; if this occurs, the following screen
will show and the unit will be prevented from
operating.
400
500
600
700 800
N
H
H
N
400
500
600
700 800
L
N
D1-2L235
D1-2N235*
D2L235
D2N235*
N/A
D2N335*
D3L335
D3N335*
D4L355
D4N355*
D4L655
D4N655*
NB VE60-3P and VE90-3P units include two cylinders.
900
1000
1100
900
1000
1100
H
D1-2H235
D2H235
N/A
D3H335
D4H355
D4H655
* Fitted as standard
1200
1200