Humidifier Location; Mounting The Humidifier - Vapac VIRTUOSO VE05-1P Installation And Operating Manual

Electrode boiler humidifier
Table of Contents

Advertisement

Humidifier location

The mechanical and electrical
installation must comply with
all local and national codes and
regulations in place at the time of
installation.
I
The appliance is designed for
indoor installation only.
For best results, the humidifier should be
installed with the following rules in mind:
Installation Do's:-
• Do ensure that the humidifier is mounted
in an accessible location that permits easy
inspection and servicing of the humidifier.
Minimum clearances detailed previously
must be maintained.
• Do ensure that the floor beneath the
humidifier is waterproof so as to withstand
any water spillage or leakage during
servicing or if a problem occurs.
• Do mount the unit as close to the steam
distribution pipe(s) as possible. The total
flexible hose steam line MUST NOT exceed 5
metres in length.
• Do mount the unit at a convenient height to
read and use the touch screen display panel.
• Do ensure the location of the unit is
well ventilated such that the ambient
temperature does not exceed 40°C or falls
below 5°C.
• Do be aware that high humidity levels
may encourage the growth of biological
organisms in the environment.
• Do use the supplied printed template to
mark the mounting hole positions.
• Do be aware of the unit weight. All
applicable handling and lifting safe practises
must be followed.
• Do remove the cylinder if necessary to access
the mounting holes in the back of the steam
section.
• Do use suitably sized wall bolts or equivalent
to mount the unit.
Page No 12 of 80
Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0
Installation Don'ts
• Don't use the handles on the side of the
casing to lift the unit.
• Don't install the humidifier where failure of
the appliance could cause damage to other
equipment or the building structure.
• Don't mount the unit close to sources of
strong electro-magnetic emissions e.g.
transformers, etc.
• Don't mount the unit in an unventilated
enclosure.
• Don't mount the unit in a location requiring
ladder access.
• Don't mount the unit within a false ceiling
or other location where a malfunction would
cause damage e.g. a water leak.
• Don't mount the unit where temperature
and humidity conditions can cause
condensation on electrical components e.g.
a cold room.
• Don't mount the unit in a location where
the sound of water flow in a pipe would
be unacceptable e.g. a library, private
apartment, etc.

Mounting the humidifier

Do not locate the humidifier where
it may be exposed to water or
where the ambient temperature
exceeds 40°C or falls below 5°C.
Ensure that the structural elements
which will be used to support the
humidifier are adequate to carry
the wet weight of the appliance
and its ancillary components.
Unit dry and wet weights are
given in the technical data section
previously.
Sufficient space must be provided
around the humidifier for access,
servicing and safety
on page 11 for
(see clearances
details).