2. Advanced mode page 2
C
• The settings on this page relate to when a
caution alarm is initiated. i.e. at the default
settings of Demand:80% and Within
Time:30mins the alarm will activate if the
system does not hit 80% demand within
30minutes of operation. These parameters
can be changed on this page.
3. Advanced mode page 3
• The settings on this page relate to when a
caution alarm is initiated. i.e. at the default
settings of Demand:60% and Within
Time:240mins the alarm will activate if
the system does not hit 60% demand
within 240minutes of operation. These
parameters can be changed on this page.
Page No 32 of 80
Vapac, Virtuoso VE Humidifier, Installation Manual, EN 2024-01, D301474 Iss 0
4. Advanced mode page 4
• This page allows the output of the unit
to be downrated as a percentage of the
capacity of the unit. The current downrated
percentage will be displayed. Pressing
the change button will bring up a screen
allowing the percentage of capacity set
point to be changed.
5. Advanced mode page 5
• The sensor offset for humidity in
percentage RH will be displayed. Pressing
the change button will bring up a screen
allowing the humidity sensor offset set
point to be changed.
• If the control input is provided by a
combined temperature and humidity
sensor, the sensor offset for temperature
in degrees centigrade will be displayed.
Pressing the change button will bring up
a screen allowing the temperature sensor
offset set point to be changed.