7-3-6. Night operation (sound reduction) control

Outdoor unit
SW1: Night time signal switch
Operation
This function decreases noise at night or other times as necessary.
Terminal
ON
OFF
COOL
(SW1)
ON
OFF
The input signal is recognized during its rising / falling phase.
(After reaching the top / bottom of the rising / falling edge, the signal must remain there for at least 100 ms.)
The system's capacity is reduced during low-noise operation.
The table below provides a rough guide to this capacity reduction.
For Europe and Turkey model
During low-noise mode*dB(A)
Outodoor unit
Cooling
0806HS8-E/TR
1006HS8-E/TR
For China model
During low-noise mode*dB(A)
Outodoor unit
Cooling
0806HT8-C*
0906HT8-C*
1006HT8-C*
* Position of noise measuring device: 1 m from the front face of the set and 1.5 m above ground (in anechoic
chambers)
Connection
Outdoor unit
cable
interface PCB
8
0
5
N
C
Input signal
Operation
Night time control
Normal operation
Heating
50
50
50
50
Heating
50
50
50
50
50
50
Locally procured
Optional PCB
TB1
COM
7
1
J
COOL
P
HEAT
Shield
wire
Capacity
Cooling
Heating
approx. 80 %
approx. 75 %
approx. 65 %
approx. 60 %
Capacity
Cooling
Heating
approx. 75 %
approx. 60 %
approx. 70 %
approx. 60 %
approx. 65 %
approx. 55 %
43
59
SW1
Relative to maximum capacity
Relative to maximum capacity