Step Component
12
Compressor
1. Removing the malfunctioning compressor
replacement
1) Collect the refrigerant gas with the recovery
equipment.
2) Remove the front panels, upper panel, discharge
cabinets, side panels, partition plate (upper), and
inverter assembly.
[Step.1, Step.2, Step.3, Step.4, and Step.5]
3) Remove the screws the inverter fixing plate
(back), heat exchanger, and remove the inverter
fixing plate (back). (M4×10, 2) (Fig. 12-1)
4) Remove the screws the partition plate and
inverter fixing plate (lower), and remove the
inverter fixing plate (lower).
(M4×10, 3) (Fig. 12-1)
5) Remove the screws the packed valve and ball
valve from the valve fixing plate.
(hexagonal screws: M5×16, each 2) (Fig. 12-2)
6) Remove the screws the partition plate (lower) and
valve fixing plate. (M4×10, 2) (Fig. 12-3)
7) Remove the sound-insulation mat (outside,
inside).
8) Remove the screws the partition plate (lower),
bottom plate, and heat exchanger (lower), and
remove the partition plate (lower).
(M4×10, 5) (Fig. 12-4)
9) Remove the TD sensor, TK sensor, TL3 sensor,
binding band and pipe cover around the
compressor. (Fig. 12-5)
10) Remove the pipe fixed rubber and the rubber
sheet. (Fig. 12-6)
11) Remove the TO sensor, TE sensor, and binding
band. (Fig. 12-6, 7)
Procedure
Pipe fixed rubber
Rubber sheet
TO sensor
TE sensor and
binding band
(Fig. 12-6)
(Fig. 12-7)
Inverter fixing plate (back)
screws (2 positions)
Inverter fixing plate (lower)
screws (3 positions)
Hexagonal screws: M5×16,4
(Fig. 12-2)
Partition plate (lower)
(Fig. 12-4)
TK sensor
164
Remarks
(Fig. 12-1)
Valve fixing plate
Ball valve
Packed valve
Valve fixing plate
(Fig. 12-3)
Partition plate
(lower)
TD sensor
TL3 sensor
(Fig. 12-5)