Step Component
4
Partition plate
WARNING
(upper)
replacement
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1. Detachment
1) Remove the front panels, upper panel and
discharge cabinets. [Step.1 and Step.2]
2) Remove the screws of the reactor (CH-90) from
terminal block.(M5×10,2) (Fig.4-1)
Remove the fast-on terminal of the reactor (CH-
98). (2 positions) (Fig.4-1)
3) Remove the screws for the partition plate (upper)
and heat exchanger's side metal plate. (Fig.4-2)
4) Lift the assembly and remove it. (Fig.4-2)
CAUTION
Disengage the locks on the housing to unplug
the connectors.
2. Attachment
1) Install it in the reverse of the procedure to
remove it.
Tighten the screws of terminal block to 1.2Nm.
Procedure
157
Remarks
Terminal
block
(Fig. 4-1)
(Fig. 4-2)
Reactor CH-90
Reactor CH-98
Partition plate
(upper)
Partition plate (upper)
Screws (2 position)