Toshiba MCY-MHP0806HT8-C Series Service Manual page 171

Table of Contents

Advertisement

Step Component
16
Heat
5) Remove the TO sensor holder , TE sensor holder,
exchanger
and bindng band to fix it. (Fig. 16-3)
assembly
6) Remove the pipe fixing rubber (2 positions),
(continued)
rubber sheet, and the binding bands. (Fig.16-3)
(Fig.16-4)
7) Using the burner, remove the header and heat
exchanger 4-way valve connecting pipe
(Fig. 16-3))
8) Using the burner, remove the liquid pipe and heat
exchanger connecting pipe. (Fig. 16-3)
CAUTION
Pay careful attention when removing the pipes
by passing the burner over the brazed areas
since if there is any oil inside the pipes, flames
may shoot out at the very moment when the
brazing melts.
9) Pull the heat exchanger 4-way valve
connecting pipe and liquid pipe upward, and
draw them out.
10) Using the burner, remove the distributor
assembly which is connected to the heat
exchanger assembly. (Fig. 16-4)
11) Using the burner, remove the header (upper)
and header (lower). (Fig. 16-4)
Procedure
170
Remarks
Header (upper)
Heat exchanger 4-way
valve connection piping
Remove with the burner
Heat exchanger (upper)
Rubber sheet
Upper and lower
header connections
Header (lower)
Heat exchanger (lower)
Distributor assembly
TO sensor holder
Liquid pipe
TE sensor holder
Remove with the burner
Heat exchanger
connecting pipe
(Fig. 16-3)
Header pipe
Suction pipe
Pipe fixed rubber
and the wrap
(2 positions)
(Fig. 16-4)

Advertisement