HMS Networks Intesis INMBSDAI001I000 User Manual page 24

Modbus rtu gateway
Table of Contents

Advertisement

Error Codes
Error Code
Error in Remote Controller
63
EE
64
EF
65
H0
66
H1
67
H2
68
H3
69
H4
70
H5
71
H6
72
H7
73
H8
74
H9
75
HA
76
HH
77
HC
79
HE
80
HF
81
F0
82
F1
83
F2
84
F3
87
F6
91
FA
92
FH
93
FC
95
FE
96
FF
97
J0
98
J1
99
J2
100
J3
101
J4
102
J5
103
J6
104
J7
105
J8
106
J9
107
JA
108
JH
109
JC
111
JE
112
JF
113
L0
116
L3
117
L4
118
L5
119
L6
120
L7
121
L8
USER MANUAL Version 1.0.0
Error Category
Error description
Malfunctions in a drain water
Ice thermal storage unit error
Malfunctions in a sensor system
Air temperature thermistor error
Sensor system of power supply error
High Pressure switch is faulty
Low pressure switch is faulty
Compressor motor overload sensor is abnormal
Compressor motor over current sensor is abnormal
Overload or over current sensor of fan motor is abnormal
Sensor system of over-current of AC input
Outdoor air thermistor system error
Discharge air thermistor system error
Pump motor sensor system of over current is abnormal
Water temperature sensor system error
Sensor system of drain water is abnormal
Ice thermal storage unit error (alarm)
No.1 and No.2 common protection device operates.
No.1 protection device operates.
No.2 protection device operates
Discharge pipe temperature is abnormal
Temperature of heat exchanger(1) abnormal
Discharge pressure abnormal
Oil temperature is abnormally high
Suction pressure abnormal
Oil pressure abnormal
Oil level abnormal
Sensor system error of refrigerant temperature
Pressure sensor error
Current sensor error
Discharge pipe thermistor system error
Low pressure equivalent saturated temperature sensor system error
Suction pipe thermistor system error
Heat exchanger(1) thermistor system error
Heat exchanger(2) thermistor system error
Oil equalizer pipe or liquid pipe thermistor system error
Double tube heat exchanger outlet or gas pipe thermistor system error
Discharge pipe pressure sensor error
Oil temperature sensor error
Suction pipe pressure sensor error
Oil pressure sensor error
Oil level sensor error
Inverter system error
Temperature rise in a switch box
Radiation fin (power transistor) temperature is too high
Compressor motor grounded or short circuit, inverter PCB fault
Compressor motor grounded or short circuit, inverter PCB fault
Over current of all inputs
Compressor over current, compressor motor wire cut
INMBSDAI001I000 Modbus RTU Gateway
Page 21 of 23

Advertisement

Table of Contents
loading
Need help?