INMBSDAI001I000 Modbus RTU Gateway
4.5. DIP Switch Configuration
See figure:
Gateway layout (page 9)
All the configuration settings on the INMBSDAI001I000 gateway can be written and read from the Modbus
interface. Some of these settings can also be set up from the gateway's onboard DIP switch blocks.
The following tables apply to the interface configuration through DIP switches:
NOTICE
DIP-Switch SW1 is not used by the current version of the INMBSDAI001I000 gateway.
Table 2. DIP switches SW3 and SW4: Modbus baud rate setting
SW3
SW4
Position
Position
1 2 3 4 5 6 7 8 1 2 3 4
X X X X X X ↑ ↑ X X ↑ X
X X X X X X ↓ ↑ X X ↑ X
X X X X X X ↑ ↓ X X ↑ X
X X X X X X ↓ ↓ X X ↑ X
X X X X X X ↑ ↑ X X ↓ X
X X X X X X ↓ ↑ X X ↓ X
X X X X X X ↑ ↓ X X ↓ X
X X X X X X ↓ ↓ X X ↓ X
Table 3. Dip switch SW4: Temperature scale and magnitude settings
SW4
Position
1
2
3
4
↑
X
X
X
↓
X
X
X
X
↑
X
X
X
↓
X
X
Table 4. Dip switch SW4: Termination resistor setting
SW4
Position
1
2
3
4
X
X
X
↑
X
X
X
↓
Page 10 of 23
Description
2400 bps
4800 bps
9600 bps (default value)
19200 bps
38400 bps
57600 bps
76800 bps
115200 bps
Description
Temperature values in Modbus
register are represented in
degrees (x1) (default value).
Temperature values in Modbus
register are represented in
degrees (x10).
Temperature values in Modbus
register are represented in
degrees Celsius (default value).
Temperature values in Modbus
register are represented in
degrees Fahrenheit.
Description
120Ω termination inactive
(default position)
120Ω termination active
DIP Switch Configuration
USER MANUAL Version 1.0.0