The following describes the devices used for CC-Link IE Field Network. For reference products of Ethernet cables and
recommended products of hubs, refer to the following.
Page 79 Component List
■Ethernet cable
Use the Ethernet cable that meets the following standards.
Ethernet cable
CC-Link IE Field Network
cable
*1
PERIPHERAL cable
*1 Use the cable that meets the following conditions.
Diameter of lead: AWG26 or higher
Shield: Copper braid shield and drain wire, or copper braid shield and aluminium layered type shield
■Hub
Use hubs that meet all the conditions listed below. Operation is not guaranteed if the hubs do not meet these conditions.
• Compliance with the IEEE802.3 (1000BASE-T)
• Support of the auto MDI/MDI-X function
• Support of the auto negotiation function
• Switching hub (layer 2 switch)
*1 A repeater hub is not available.
Wiring of connector
Specialised tools are not required for wiring the external forced stop cable connector because plugs with spring connection
are used.
■Applicable wire size and wire fabrication
• Applicable wire size
The applicable wire size for external forced stop cable connector is shown below.
Connector
External forced stop cable connector
• Wire fabrication
Strip the wire according to stripped length indicated in the figure below.
Slide the sheath off the wire and gently twist and straighten the strands. When using the wire, be careful not to short with stray
strands entering the neighbouring poles. Do not use solder on the wire's core as this may lead to insufficient contact.
Sheath
Core
Approx.
8 mm (0.31 inch)
[Using a ferrule]
A ferrule can also be used to connect with the connector.
Use the ferrules in the table below for the external forced stop cable connector.
Connector
External forced stop cable
connector
Cut the wire sticking out from the end of the ferrule to 0.5 mm (0.02 inch) or less.
6 WIRING
48
Category 5e or higher, STP cable
(double shielded)
Category 5 or higher, STP cable
*1
Type
FK-MC0,5/3-ST-2,5
Wire size
Ferrule model
For 1 wire
AWG21
AI0.5-8 OG
0.5 mm (0.02 inch) or less
Connector
Cable
RJ45
Straight cable
connector
RJ45
Straight cable
connector
Crossover cable (direct
connection)
Applicable wire size
0.08 to 0.5 mm
Crimping tool
For 2 wires
CRIMPFOX-ZA3
Standard
• IEEE802.3 (1000BASE-T)
• ANSI/TIA/EIA-568-B (Category 5e)
• 100BASE-TX
2
(AWG28 to AWG20)
Manufacturer
PHOENIX CONTACT GmbH & Co. KG