CIB UNIGAS RX92R-FGR Manual page 26

Gas burners
Table of Contents

Advertisement

PART II: INSTALLATION
BURNERS WITH INVERTER VARIANT (if provided)
DANFOSS
The LMV51.300 / LMV52.xxx e LMV37.400/LMV26.300 electronic cam burners with fan motor driven by inverter in addition to the air
and fuel adjustment curves also have a fan motor speed adjustment curve.
The LMV5x equipment through a sensor controls the fan motor revolutions and with a signal in 4÷20mA controls it through the inverter.
The LMV2x equipment through a sensor controls the fan motor revolutions and with a signal in 0÷10V controls it through the inverter.
Generally the curve of the inverter goes from 50% to 100% of the engine revolutions. This, in addition to improving the setting of the
burner also allows a saving on the consumption of the fan engine..
Two series of interchangeable Inverters
version with Inverter FC101 and FC102
Terminal interface with Inverter
LMV5
Tipo
XXXXX
XXXXX
LMV5
XXXXX
XXXXX
XXXXX
LMV2x/3x
XXXXX
Danfoss FC102
26
Modello
M-. MD. xx. xx. x. x. xxx. EI.
M-. MD. xx. xx. x. x. xxx. EG.
MG. MD. xx. xx. x. x. xxx. EK.
MG. MD. xx. xx. x. x. xxx. ER.
M-. MD. xx. xx. x. x. xxx. EB.
MG. MD. xx. xx. x. x. xxx. EC.
Danfoss FC101
Braking resistances
possibility of use only for FC102
LMV2x/3x