Industrial Computers and Thin Clients for Hazardous Locations, Series J
Catalog Numbers 6181X-000NWNNDNB-3xNNNNxG-xxx(x), 6181X-000NWNNDNB-3xxxxxxG-xxx(x), 6181X-121PPMXDNB-3xNNNNxG-xxx(x), and
6181X-121PPMXDNB-3xxxxxxG-xxx(x)
Topic
Read this document and the documents that are listed in the
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition
to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably
trained personnel in accordance.

Installation Precautions

Read and follow these precautions before you install your industrial computer or thin client for hazardous locations.
Environment and Enclosure Information
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in 
IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 32 and ABNT NBR IEC/CISPR 32. Without appropriate
precautions, there can be potential difficulties with electromagnetic compatibility in other environments due to conducted and radiated disturbance.
The equipment must be panel mounted or open-type, and installed in a tool-only accessible enclosure that is suitable for the environment.
All 6181X-121 integrated display industrial computers and 6181X-121 integrated display thin clients are shipped with a gasketed bezel to meet specified
ratings when mounted in a panel or enclosure with an equivalent rating. For more information about these ratings, 
see
Hazardous Location Information on page
In addition to this publication, see the following:
• Publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines, for more installation requirements
• ABNT NBR IEC 60529, NEMA 250, UL 50, and IEC 60529, as applicable to your region, for explanations of the degrees of protection that are provided by
enclosures
European Union Directive/United Kingdom Regulations
These industrial computers and thin clients meet the European Union Directive requirements when installed within the European Union or EEA regions and has the CE
marking. Additionally, these industrial computers and thin clients meet the United Kingdom regulation requirements when installed within the United Kingdom and has the
UKCA marking. Copies of the declarations of conformity are available at rok.auto/certifications.
ATTENTION: To comply with EN 55024 and EN 55032, the following applies to cable usage:
• USB cables must be less than 3 m (9.84 ft) long
• All I/O cables, except for Ethernet cables, must be used indoors
• All I/O cables, except for Ethernet cables, cannot exit the building at any point and cannot directly connect to cables outside the building
To comply with EN 55024 and EN 55032, use the following for cable types:
Cable Type
Required Attribute
LAN
Shielded or unshielded
USB
2.
Cable Type
Serial RS-232
Shielded
Page
1
2
3
5
5
8
9
10
14
Additional Resources
section about installation, configuration, and operation of this equipment
Required Attribute
Shielded
DVI
Shielded
Cable Type
Required Attribute
DisplayPort
Shielded
DC Power
Unshielded

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Allen-Bradley 6181X-000NWNNDNB-3xNNNN G Series

  • Page 1: Table Of Contents

    Installation Instructions Original Instructions Industrial Computers and Thin Clients for Hazardous Locations, Series J Catalog Numbers 6181X-000NWNNDNB-3xNNNNxG-xxx(x), 6181X-000NWNNDNB-3xxxxxxG-xxx(x), 6181X-121PPMXDNB-3xNNNNxG-xxx(x), and 6181X-121PPMXDNB-3xxxxxxG-xxx(x) Topic Page Installation Precautions Hazardous Location Information Installation Requirements Prepare for Installation Mount Your Product Connect Your Product Complete the Installation Technical Specifications Additional Resources Read this document and the documents that are listed in the...
  • Page 2: Hazardous Location Information

    UV radiation, and greatly increase its field life. IMPORTANT The Rockwell Automation approved sun shield, Cat. No. 6189X-SUNSHIELD, must be used if your integrated display model is exposed to direct sunlight.
  • Page 3: Installation Requirements

    • PCIe and PCI add-in cards must be rated Class I, Division 2, T4 (max), 4 W (max), 90 °C (194 °F) (min) surrounding ambient temperature. Hot Surfaces IMPORTANT The Rockwell Automation approved sun shield, Cat. No. 6189X-SUNSHIELD, must be used if your integrated display model is exposed to direct sunlight. Restricted Access Location Verify that restricted access locations for the equipment meet these conditions: •...
  • Page 4 (including the touch screen and LCD panel) is shortened. • The relative humidity of the ambient air must not exceed the limits that are specified in Table 3 and must avoid condensation. Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 5: Prepare For Installation

    Mounting Position • When mounted, your integrated display model cannot be: - tilted from vertical (see Figure - mounted on a horizontal surface. • Choose an ergonomic height suitable for the end user. Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 6 ATTENTION: Do not overtighten the mounting clips. Overtightening causes damage to the gasket. Tighten the mounting clips to the specified torque to provide a proper seal to help prevent water or chemical damage to your industrial computer or thin client. Rockwell Automation assumes no responsibility for water or chemical damage to your industrial computer or thin client and any other equipment within the enclosure because of improper installation.
  • Page 7 Tighten the M4 panhead screws with grommets in the same sequence to a torque that is appropriate for the screw and wall material. If your non-display model is attached to steel material, the recommended torque of the M4 panhead screws with grommets is  1.13…1.36 N•m (10…12 lb•in). Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 8: Connect Your Product

    In industrial environments, proper cable routing and power conditioning are required for Ethernet communication. Rockwell Automation recommends that you route all Ethernet cable through dedicated metal conduits. For improved performance reliability, install ferrite bead filters at the cable ends.
  • Page 9: Complete The Installation

    If Microsoft Windows® 10 Internet of Things (IoT) Enterprise 2021 LTSC (64 bit) was factory installed: Read and accept the end user setup procedure. WARNING: Do not disconnect power from the system until after the Microsoft Windows setup procedure is completed. If power is disconnected during the setup procedure your system image can become corrupt. Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 10: Technical Specifications

    12.1 inch integrated display panel thin client, PCAP multi-touch touch screen, aluminum bezel, Intel Core i3 6181X-121PPMXDNB-3ANNNNFG-N1S Integrated Display processor, 16 GB RAM, fTPM, DC power, without SSD, without OS, without Rockwell Automation software bundle Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 11 (7.50) (9.88) (9.88) 75.4 Top View (2.97) 83.4 101.3 320.0 Top View (3.28) (4.00) (12.60) 320.2 (12.61) 16.4 16.4 (0.65) (0.65) 115.0 115.0 87.1 87.1 87.1 (4.30) (4.30) (3.43) (3.43) (3.43) Technical Specifications Rockwell Automation Publication 6181X-IN003A-EN-P - October 2023...
  • Page 12 Industrial Computers and Thin Clients for Hazardous Locations Installation Instructions Certifications This equipment meets the following certifications. For the most current information on all certifications, visit the Rockwell Automation Product Certifications website at rok.auto/certifications Turkey RoHS (EEE Yönetmeliğine Uygundur. In Conformity with the EEE Regulation)
  • Page 13 2 LAN ports (RJ45), 1 GB each Lithium RTC battery IMPURTANT: The lithium battery can only be replaced by Rockwell Automation. Return your product in its original inner and outer packaging to Real-time clock (RTC) Battery Rockwell Automation for battery replacement. For return information, contact your local distributor or Rockwell Automation representative, or...
  • Page 14: Additional Resources

    For a complete list of accessories and accessory installation instructions, see Accessories for Industrial Computers and Thin Clients for Hazardous Locations, Series J Product Information, publication 6181X-PC002. Additional Resources These documents contain additional information to related products from Rockwell Automation. You can view or download publications at rok.auto/literature. Resource...

This manual is also suitable for:

Allen-bradley 6181x-000nwnndnb-3 g seriesAllen-bradley 6181x-121ppmxdnb-3 nnnn g seriesAllen-bradley 6181x-121ppmxdnb-3 g series

Table of Contents