Sinclair ASDH-96AI Installation Manual page 7

High static pressure duct
Hide thumbs Also See for ASDH-96AI:
Table of Contents

Advertisement

Lifting
Hoisting rope
(belt)
4.2 Installation place
Please keep away from the following place, or malfunction of the
machine may be caused:
There is combustible gas leakage.
There is much oil (including engine oil) ingredient.
There is salty air surrounding(near the coast)
There is caustic gas (the sulfide, for example) existing in the
air (near a hotspring)
A place the heat air expelled out from the outdoor unit can
reach your neighbor's window.
A place that the noise interferes your neighbors every day
life.
A place that is too weak to bear the weight of the unit
Uneven place.
Insufficient ventilation place.
Near a private power station or high Frequency equipment.
Install indoor unit, outdoor unit, power cord and connecting
wire at least 1m away from TV set or radio to prevent noise or
picture interference.
The insulation of the metal parts of the building and the air
conditioner should comply with the regulation of National Electric
Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and
noise in those electrical appliances. (Noise may be
generated depending on the conditions under which the
electric wave is generated, even if 1 meter is kept.)
4.3 Installation space (Unit:mm)
hook
In the lifting process, without
removal of cartons and other
packaging to avoid damage to
the product appearance.
Center of gravity
As shown illustrating the rope must
pass through the inside of the circle
two wooden support stakes, to avoid
rope slip danger in lifting process.
Fig.4-1
1120
Single unit installation
(Wall or obstacle)
Air inlet
>300
Air inlet
Parallel connect the two units or above
>300
>600
>3000
Parallel connect the front with rear sides
>3000
>1000
4.4 Moving and installation
Since the gravity center of the unit is not at its physical center,
so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45°, and do not lay it sidelong.
Make concrete foundation according to the sepecifications of
the outdoor units.(refer to Fig.4-6)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.
(refer to Fig.4-6)
668
206
Maintain the electric
wire and pipeline
>600
Air outlet
>6000
>4000
Fix with bolt
(Unit:mm)
>300
5

Advertisement

Table of Contents
loading

Table of Contents