Huawei MTS9300A User Manual page 46

Hide thumbs Also See for MTS9300A:
Table of Contents

Advertisement

MTS9300A Telecom Power (Ooredoo, Indonesia,
MTS9304A-HD2002)
User Manual
Silk
Screen
DO2
Activation and Startup
An ESM can be activated in three modes. After being activated, the ESM switches
from the sleep mode to disconnected mode.
Technical Specifications
Table 3-21 Technical specifications
Item
Dimensions (W x D
x H)
Weight
Installation mode
Maintenance mode
Humidity
Altitude
Issue 06 (2021-10-13)
Definition
Overload
warning,
overdischar
ge
protection
Activation through the PWR terminal: supply 43.2–58 V DC power to the PWR
terminal on the ESM panel for at least 5s.
Activation through the MANUAL ON/OFF button: hold down the MANUAL
ON/OFF button on the ESM panel for at least 5s and less than 15s.
Activation through the power port: supply a DC voltage of 43.2–58 V to the
power terminal on the front panel for at least 5s.
NO TE
1. The MANUAL ON/OFF button is a contact button. The interval for pressing the
button should be greater than 0.5s; otherwise, the operation is ineffective.
2. If you have forcibly powered off the battery that is in charging, discharging, or
disconnected mode by pressing the MANUAL ON/OFF button, the ESM can be only
reactivated by pressing and holding this button.
Specifications
● 442 mm x 396 mm x 130 mm (excluding mounting
● 482 mm x 396 mm x 130 mm (including mounting
44 kg
Installed in a 19-inch rack
Maintained from the front
5%–95%
0–4000 m (When the altitude ranges from 2000 m to
4000 m, the highest operating temperature decreases by
1°C for each additional 200 m.)
Copyright © Huawei Technologies Co., Ltd.
Description
If the ESM raises one of the following
alarms, the dry contact supplies an
alarm signal:
Discharge undervoltage alarm,
discharge undervoltage protection, and
discharge overcurrent warning
ears)
ears)
3 Components
Alarm
Status
40