10. Installation
Choosing the installation location
Module installation
• For <Case 1> or <Case 3>
– Height of the wall on the front side should not be higher than 1500mm (60inch).
– Height of the wall on the air inlet side should not be higher than 500mm (20inch).
– Height of the wall on the side is not limited.
– If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded height] should be added to the service space (S1, S2).
Over
Front
100 (4)
side
Over 100(4)
<Case 1>
Over 300 (12)
Over 400
Over 400
Front
(16)
side
<Case 2>
Over 100 (4)Over 100 (4)
Over 100 (4)
Front side
Over 100 (4)
Over 100 (4) Over 100 (4)
Front side
<Case 3>
S1+h1/2
Unit : mm (inch)
Over 100 (4)
Height of
the wall is
unlimited
(16)
Over 100
(4)
Over 100
(4)
Unit : mm (inch)
S2+h2/2