10. Installation
Choosing the installation location
Outdoor unit location requirements
Decide the installation location, with the consideration of the following conditions, under user's approval.
• Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in
residential areas, keep the operation hours in mind.)
• Place where structure can bear the weight and vibration of the outdoor unit.
• Place with flat surface where rainwater does not settle or leak.
• Place where it is not exposed to strong wind.
• Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct must be
purchased separately in your local market.)
• Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
• Place where it allows easy waterproofing and draining work for the condensation water generated from the
outdoor unit during heating operation.
• Place where there is no risk of inflammable gas leakage.
• Place where there is no direct influence of snow or rain.
• Place where a large amount of water generated by external environment does not directly affect the top of the
outdoor unit
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
1 Do not install the product in a place where it is directly exposed to sea water and sea breeze.
– Make sure to install the product behind a structure (such as building) that can block see breeze.
– Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed
to sea breeze by installing a protection wall.
2 Consider that the salinity particles clinging to the external panels should be sufficiently washed out.
3 Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that
the slope does not disturb drainage.
– Keep the floor level so that rain does not accumulate.
– Be careful not to block the drain hole due to foreign substance
4 When product is installed in seashore, periodically clean it with water to remove attached salinity.
5 Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the
base part has good drainage.
6 If the product is damaged during the installation or maintenance, make sure to repair it
Protection wall
Sea breeze
Outdoor unit
Sea
Protection wall should be constructed with a solid material that can
block the sea breeze and the height and width of the wall should be 1.5
times larger than the size of the outdoor unit. (You must secure more
than 700mm (28inch) of space between the protection wall and the
outdoor unit for air circulation.)
Outdoor
unit

Advertisement

Table of Contents
loading

Table of Contents