10. Installation
Choosing the installation location
7 Check the condition of the product periodically.
– Check the installation site every 3 months and perform anticorrosiontreatment such as R-Pro supplied by
SAMSUNG (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product
condition.
– When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate
measures like covering the product.
8 If the product installed within 500m (1640ft) of seashore, special anticorrosiontreatment is required.
※ Please contact your local SAMSUNG representative for further details.
If you cannot find a proper location to install the outdoor unit, consult with an expert or specialty store.
CAUTION
• System air conditioner may cause static noise when listening to AM stations. Therefore, select an installation
location for indoor unit where electrical wiring can be done while keeping certain distance from a radio,
computer and stereo equipment.
– Especially, keep the unit at least 3m (9.84ft) away from the electrical equipment in an area with weak
electromagnetic waves and put the main power cable and communication cables in a separately installed
protection tube.
– Make sure that there is no equipment that generates electromagnetic waves. If not electromagnetic waves
may cause problem to the control systems which may lead to air conditioner malfunction.
(Example: Remote control sensor of the indoor unit may not receive the signal very well, due to ballast
stabilizer of the lighting equipment.)
• In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns of direct
snowfall on the outdoor unit. Also, build higher base support so that accumulated snow does not block the air
inlet or the heat exchanger.
• R-410A refrigerant is a safe, nontoxic and nonflammable refrigerant. However, if the place holds any concerns
for exceeding dangerous level of refrigerant concentration in case of refrigerant leakage, extra ventilation
system is required.
• When you install the outdoor unit in high places such as a roof, install fence or guardrail around it. When there
is no fence or guardrail, service person could fall.
Sea breeze
Sea
Sea breeze
Sea
Outdoor unit
Outdoor
unit
Outdoor
unit