Programming The P.c.b - Immergas VICTRIX EXA 28 1 ERP Instruction Booklet And Warning

Table of Contents

Advertisement

3.11 PROGRAMMING THE P.C.B.

The boiler is prepared for possible programming of several op-
eration parameters. By modifying these parameters as described
below, the boiler can be adapted according to specific needs.
To access the programming stage, set the DHW selector (5) in
the "6" position and the heating selector (6) in the "9" position
and press the "Reset" (3) and "Summer/Winter" (2) buttons for
about 8 seconds.
Once the menu has been accessed, it is possible to scroll through
the three sub-menus present (s, p, t) by pressing the "Summer/
Winter" (2) button for 1 second.
Id
Parameter
Parameter
Minimum DHW
S0
output
Maximum DHW
S1
output
S2
Minimum CH output
S3
Maximum CH output
Power
S4
block
Central heating set
S5
point minimum
temperature
Central heating set
point
S6
maximum
temperature
External probe
S7
correction
S8
Boiler power
Fan speed for ignition
S9
consent (no. of igni-
tion consent revs)
Description
The boiler also has electronic modulation that adapts the boiler
potentiality to the effective heating demand of the house. Therefore
the boiler works normally in a variable gas pressure field between
minimum and maximum power depending on the system heat
load, setting fan speed (in rpm, hundreds of revs are represented
on the display).
N.B.: the boiler is produced and calibrated in the central heating
phase at nominal output. Approximately 10 minutes are needed to
reach the nominal heat output, which can be changed using the
parameter (S3).
N.B.: selection of parameters in the presence of requests, allows
boiler functioning with current equal to the respective value.
Defines the minimum flow temperature.
Defines the maximum flow temperature.
If the reading of the external probe is not correct it is possible to
correct it in order to compensate any environmental factors.
(Over the value of +9 the display shows "CE", which enables an
external control function of the boiler for coupling of the same
with a system supervisor)
Identifies the boiler's power (only useful with a coupled storage
tank and parameter P0=1).
Identifies the speed assumed by the fan to check the state of
obstruction of the flue.
Use the ''D.H.W. regulator'' selector (5) to select the parameter
(within the same sub-menu) and rotate the ''C.H. regulator'' se-
lector (6) to alter the value.
Press the "Reset" (3) button for 1 second to store the altered
parameters.
If the parameters are stored successfully, "88" appears on the
indicator (14) for 2 seconds.
Exit the programming mode by waiting for 15 minutes or by
pressing the "Reset" (3) and "Summer/Winter" (2) buttons at the
same time.
900 ÷ 1500
20 ÷ 50 °C
(S5+5) ÷
-9 ÷ 9 K
0 = 12 kW
1 = 26 kW
2 = 28 kW
3 = 32 kW
1500 ÷ 6100
Personalized
Range
Default
Victrix Exa 28
1ErP=1400
Victrix Exa 32
1ErP=1200
28 1ErP
G20 = 5300
G31 = 5300
3500 ÷
6100
32 1ErP
G20 = 4050
G31 = 4050
Victrix Exa 28
1ErP=1400
S0 ÷ S3
Victrix Exa 32
1ErP=1200
Victrix Exa 28
1ErP=4600
S2 ÷ S1
Victrix Exa 32
1ErP=3600
Victrix Exa 28
1ErP=2000
1500 ÷
3500
Victrix Exa 32
1ErP=2300
25
85
85 °C
0
1
Victrix Exa 28
1ErP=5500
Victrix Exa 32
1ErP=4500
value
53