Immergas VICTRIX EXA 28 1 ERP Instruction Booklet And Warning page 29

Table of Contents

Advertisement

Technical data.
- The dimensions of the shafts must ensure a minimum gap be-
tween the outer wall of the smoke duct and the inner wall of the
shaft: 30 mm for circular section shafts and 20 mm in the event
of a square section shaft (Fig. 25).
- Maximum 2 changes of direction are allowed on the vertical
section of the flue system with a maximum clearance angle of
30° with respect to the vertical.
- The maximum vertical extension using a Ø 60 ducting system is
13 m, the maximum extension includes 1 bend Ø 60/10 at 90°,
1 m of horizontal pipe 60/100, 1 90° ducted bend Ø 60 and the
roof terminal for ducting.
To determine the C
flue system in configurations other than
93
that described (Fig. 27) one must consider that 1 metre of ducted
pipe according to the indications described has a resistance factor
equal to 4.9.
- The maximum vertical extension using a Ø 80 ducting system
is 28 m, the maximum extension includes 1 adapter 60/100 to
80/125, 1 87° bend Ø 80/125, 1 m of horizontal pipe 80/125, 1
90° ducted bend Ø 80 and the roof terminal for ducting.
To determine the C
flue system in configurations other than
93
that described (Fig. 27) one must consider the following head
losses:
- 1 m of concentric pipe Ø 80/125 = 1 m of ducted pipe;
- 1 87° bend = 1.4 m of ducted pipe;
Consequently one must subtract the equivalent length of the
part added to the 28 m available.
X
C
93
27
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Victrix exa 32 1 erp

Table of Contents