Connecting a DGE601A52
DGE601A51 only
If the system needs to control many air conditioners, use DGE601A52 to connect them.
You can connect up to 64 air conditioners to 1 DIII port. Because it is possible to connect
to 2 ports on 1 DGE601A51, the number of indoor units you can control with 1 DGE601A51
is up to 128.
By using DGE601A52 or DGE601A53, you can add 64 indoor units.
Using all 8 DIII ports, you can connect and control a total of 512 indoor units at maximum.
• Be sure to perform the operation during power-off conditions. Not doing so
• Do not clamp high-current cables together with low-current cables.
3.2.1

Terminals location and schematic connection diagram

Connect the DGE601A52 to the [plus ADP IF] terminals located on the front face. Be sure
to connect the positive wire to the "D+" terminal and the negative wire to the "D–" termi­
nal, respectively, as these terminals have polarity.
The DGE601A51 must be connected as a terminal to the wiring.
<Terminals location and schematic connection diagram>
A
B
C
D
E
3.2.2

Wiring specifications

• Cable type: CPEV or FCPEV cable
• Core thickness: φ0.65 ­ 0.9 mm
• Cable length: 50 m or less
24
WARNING
may cause an electric shock.
C
DGE601A51
DGE601A52
plus ADP IF (DGE601A51)
plus ADP IF (DGE601A52)
DGE601A52/DGE601A53 on which termination resistor must be enabled
(For details, refer to "DGE601A52 Installation Manual (3P581074-2)" or
"DGE601A53 Installation Manual (3P583694-2)".)
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
D
A
B
E
English

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dge602a51

Table of Contents