3.1.1

Terminals location and schematic connection diagram

To connect the DIII­NET communication line, use [F1] and [F2] terminals that are located
on the front face and indicated with [DIII-1] and [DIII-2
nals have no polarity.
An example of connecting more than two air conditioning devices is shown in the following
schematic connection diagram.
<Schematic connection diagram with air conditioners>
A
B
C
D
E
F
G
English
Outdoor unit
OUT - OUT communication (terminal)
IN - OUT communication (terminal)
Indoor unit
A maximum of 16 indoor units can be connected to 1 remote controller group.
A remote controller group can connect a maximum of 64 groups (64 indoor units) to
each DIII­NET communication line.
When connecting an additional centralised controller
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
]. These 2 termi­
DGE601A51 only
G
E
F
MONITOR
F1 F2
21