3.1.2

Wiring specifications

• Cable type: 2-core vinyl-insulated vinyl-sheathed cable/vinyl cabtyre cable or 2-core
shielded cable
• Core thickness: 0.75 ­ 1.25 mm²
• Do not use multicore cables with 3 or more cores.
• When using a shielded cable, connect only one end of each shield wire to the earth.
• The maximum wire distance must be kept to 1000 m or less, and the total wire
3.1.3

Precautions for using multiple centralised controllers

"Centralised controller" refers to the equipment (e.g. the DGE601A51) that controls
multiple air conditioners. Besides the DGE601A51, DAIKIN's product portfolio includes a
wide range of centralised controllers suitable for different applications or building sizes,
which can be used in combination to construct an optimal air conditioning control system.
If multiple centralised controllers are connected on the DIII­NET network, you must set the
"MAIN (MASTER)" and "SUB (SLAVE)" relationship for those controllers.
Set only one of those controllers as "MAIN (MASTER)", and the other controllers as
"SUB (SLAVE)".
The [DIII-1] and [DIII-2] switches
located on the front face of the DGE601A51. The
switches in the [ON] position set it as "MAIN" and
the switches in the [OFF] position set it as "SUB".
When installing multiple centralised controllers, set only the highest­priority controller as
"MAIN (MASTER)" and all other controllers as "SUB (SLAVE)" according to the follow­
ing order of priority.
High
Priority
Low
Centralised controllers that cannot be connected to the same network as the DGE601A51:
• CALCULATE UNIT
• intelligent Processing Unit
• Parallel Interface
• Intelligent Touch Controller
• DIII­NET Plus Adapter
• Residential Central Remote Controller
• Schedule Timer
• Wiring Adaptor for Electrical Appendices (1) (KRP2)
English
CAUTION
length must be limited to 2000 m or less.
However, when using a shielded cable, the total wire length must be kept to
1500 m or less.
(1) Interface for use in BACnet
(2) Interface for use in LONWORKS
(3) Intelligent Touch Manager
iTM plus adaptor
DGE601A52
(4) DGE601A51
(5) Central Remote Controller
(6) ON/OFF Controller
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
< DIII-1
/DIII-2
are

DGE601A51 only

DGE601A51 only
>
INIT
23