Connecting to equipment which inputs output contact
points
By way of the output contact points on the DGE601A51, you can control other equipment,
by connecting to the contact input points on the other equipment.
• Be sure to perform the operation during power-off conditions. Not doing so
• Do not clamp high-current cables together with low-current cables.
3.5.1

Terminals location and schematic connection diagram

<Schematic drawing of Do connection>
A
Connect the contact output lines to the [1a] [1b] [2a] [2b] [3a
DGE601A51 only
Connect [1a] to [1b], [2a] to [2b], and [3a] to [3b].
Be sure to insert a diode on both ends of the relay coil. (A diode built­in type is recom­
mended)
Contact point specifications
• Non­voltage contact point
• Voltage: 24 V DC Maximum load current: 50 mA
3.5.2

Wiring specifications

• Cable type: CPEV cable, FCPEV cable, CVV(S) cable
• Core thickness: CPEV cable, FCPEV cable: φ0.65 ­ 0.9 mm
• Cable length: 200 m or less
English
WARNING
may cause an electric shock.
A
Do
] terminals of Do located on the upper part of the front face.
CVV(S) cable: 0.75 - 1.25 mm²
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
Load L1 to L3 example
Operation lamp
Buzzer
DGE601A51
Field supply
Do
Z1
1a
1b
Z2
2a
2b
Z3
3a
3b
Lighting
Fan
L1
Z1
L2
Z2
L3
Z3
] [3b
DGE601A51 only
29