III. Device operation configuration.
If you have successfully connected to the control panel, you can proceed
to the device configuration.
Set the operating range of the device by moving the orange points on
the temperature scale. The device will start the heating system when
the temperature drops below set point and will start the cooling system
when the temperature rises above the set point.
Set the alarm range of the device by moving the red points on the
temperature scale. The device will sound an alarm and send an e-mail
and push notification to your mobile device when the temperature drops
below or changes above the set range.
(Default is 24 - 26 °C and alarms when the temperature is below 23 °C or above 27 °C)
You can select the unit from Celsius or Fahrenheit.
Set the audible alarm to on or off and proceed to the next step.
ATTENTION! For safety reasons, the audible alarm should always be on to alert you when the
water temperature changes.
Manual Thermo control
Reef Factory 2023
©
9