Page 1
178 122 35-4 CR00635 2023-07–03 Providing sustainable energy solutions worldwide Installation- and maintenance instruction BFG 1-2 H3 Biogas LME23.331C2 DMV-DLE 507 MVD 210 FRS 510 VPS 504 Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\ nedladdning eller scanna or scan QR-code. download eller scan QR-koden.
2.6 Working field .................. 8 DMV-DLE 525/11 ................. 27 Setting for nozzle assembly and air damper ......9 Gas solenoid valve MVD 210/5 / MVD 215/5 ....29 Components ................. 10 Gas pressure regulator .............31 Skeleton diagram 2-stage burner, Biogas ......12 2.10 Adjusting the gas train ...............
Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 172 515 01-2 2021-10-05 Bentone...
Prevent open flames or sparking, e.g. do not turn lights on or off, do • not use any electrical appliances or mobile phones. • Evacuate the building. Notify the installer or gas supplier of the problem so that it can be • rectified. Bentone...
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air intake to the air duct that opens into an appropriate location. Installation must be done so it does not prevent air supply to the burner. Bentone BFG 1...
Air damper, first stage Air damper, second stage Scale Brake plate adjustment 22,0 20,0 18,0 16,0 14,0 12,0 10,0 Scale value valid at 0 mbar in furnace pressure. Burner output Bentone BFG 1...
Components Flame tube Connection gas valve Safety valve Gas pressure switch Gas valve Pressure regulator Filter Ball valve Ignition transformer Motor Capacitor Bentone BFG 1...
Page 11
Screw for dividing the burner Air intake Electric connection, stage 2 Electric connection, stage 1 Air flow indicator Air regulation, stage 1 Nozzle assembly Brake plate Air regulation, stage 2 Air pressure switch Ignition electrodes Gas burner control Nozzle Reset button Bentone BFG 1...
Pressure regulator Main flow restrictor stage 1 Pressure outlet (min load) Gas valve Hydraulic brake stage 1 to 2 Leakage control (VPS) Safety valve on-off Gas pressure switch Pe Pa Pressure before valve Pressure between valves 172 515 72-2 Bentone...
If this is screwed in, the gas flow to the burner is increased by lifting the valve. This valve is always open and this opening is what gives the min-load. Adjust the air damper for stage 1 for good combustion. Bentone...
The cables of the safety system must be separated so that the outgoing signal is not placed in the same cable as the incoming signal. Wiring diagram Brown Blue Green Yellow Gn/Ye Green/Yellow Black Grey White Orange Violet 172 615 85-3 Bentone...
Postignition time 2.5 s Safety lockout time < 3 s Reset time after lockout < 1 s Reaction time on fl ame failure < 1 s Min. ionisation current at fl ame 5 µA Max. ionisation current 20 µA Bentone...
> 3 s 3.4.3 Limiting of starting repetitions LME 11... has a function with start repetition if the flame is not created at start or disappears during operation.. LME 11... allows max. three repetitions during continuous starting cycle. Bentone...
Page 17
To change to interface mode, press and hold the reset button longer than 3 s. To go back to the normal position, press and hold the reset button longer than 3 s. If the gas burner control is in the alarm position, it is reset by pressing the reset button 0.5...3 s. Bentone...
Connection must be done in accordance with the applicable • regulations. • Connection must conform to the wiring diagram. If any electrical connection other than that recommended by Enertech is used, there is a risk of property damage and personal injury. 172 535 09-2 Bentone...
X2 according to the wiring diagram. Turn off the main switch. Connect the Eurostecker X2 acc. to Alt. 1 - 3, (see Electric equipment). Install the Eurostecker X2 on the burner. Turn on the main switch. 172 525 26-2 Bentone BFG 1...
1.5 x max inlet pressure or min. 150 mbar. If leaks are found during measurement, locate the source using soapy water or leak detection spray. After sealing: check the tightness of the gas fixture again. Check the gas tightness. Bentone BFG 1...
Butan 32.25 116.09 Natural gas 29.25 Propan 24.44 88.00 Biogas 21.60 Lower calorific value H at normal conditions 15 °C and 1013 mbar, EN 676. For exact calorific value of the gas, contact the gas distributor. 172 535 48 Bentone...
The adjustment should be performed alternately: first adjustment of the minimum load followed by adjustment of the maximum load and then repeat the procedure unless acceptable combustion is achieved. 172 525 46-3 Bentone BFG 1...
Recommended air excess at basic setting Excess air flue gases% O Gas quality Natural gas Propane 4 ±1 Butane Liquefied petroleum gas Biogas Bentone BFG 1...
Measure and note the lowest air pressure in the entire work area. Set the air pressure switch to about 10-15% lower than the lowest noted pressure. Test run the burner and check the function in the entire work area. Refit protective cover. 172 535 11-2 Bentone...
When the gas pressure switch stops the burner, the measured value must approximately correspond to the setting on the gas pressure switch. Open ball valve. Remove manometer and close measuring socket. Refit protective cover. Check gas tightness. 172 535 12-2 Bentone...
Electrical connection IEC 730-1 (VDE 0631 T1) Technical data Volt U n ~(AC) 230 V Valve 2 x Class A Ambient temperature -15 °C … +60 °C Family 1 + 2 + 3 Max. operating pressure 500 mbar 172 515 67-2 2023-03-08 Bentone...
S kuiva. / Uden jernfrit metal, S tørt. / Fri S torr. / Fritt for ikke-jern-metaller, S, tørr. DMV-DLE 525/11 Pressure outlet 1, 2, 3, 5 aan kor- mukaisella kan også Peitetty liitosreikä järjestelmän kruvarna Bentone Skjult forbindelsesboring til sy...
Page 28
1 - 5. Replace solenoid Important: Make sure that the solenoid no. and voltage are correct! Remount hydraulic brake or adjust-ing plate as described on page 6. ”Replacing the hydraulic brake or adjusting plate”, steps 7 -11. Bentone...
Gas solenoid valve MVD 210/5 / MVD 215/5 8.3.1 Installation position 8.3.2 Electrical connection Grounding acc. local regulations. AC 8.3.3 Pressure taps 2 3 4 Only flange version from DN 25 Sealing plug G3/4 DIN ISO 228 Sealing plug G1/4 DIN ISO 228 Connection for C.P.I.
Page 30
Setting the main flow 8.3.5 Loosen Do not use any force Bentone...
Max. operating pressure 500 mbar Pressure regulator Class A Ambient temperature -15 °C … +70 °C Inlet pressure range 5 - 500 mbar Family 1 + 2 + 3 Outlet pressure range 2,5 - 200 mbar 172 515 66 2018-01-02 Bentone...
Page 32
Turn spindle to stop. Unscrew complete adjustment device B and remove spring C. Insert new spring D. Assemble complete adjustment device and adjust desired off-set. Screw on protective cap A. Stick adhesive label E onto typeplate. Attach lead seal. Bentone...
The red LED is lit as long as the contact is released by the regulator (heat requirement). After a short voltage drop during testing or during burner operation, an automatic restart is performed. Pressure buildup Operation Programmer Idle state 172 615 10 2018-01-15 Bentone...
Release signal Fault signal 10.3 Electrical connection The VPS 504 is connected in series between the temperature regulator and the control box via a 7-pin plug connector. See wiring diagram! Tight Untight Lock-out Operation Outlet Operating voltage ~(AC) 230V 50Hz Bentone...
Replacement upon fault detection Gas pressure switch 10 years 250,000 starts Safety blow-off system 10 years Damper motor 500,000 starts Contactor 10 years 500,000 starts The burner and its components must be recycled according to applicable regulations. 172 615 88-2 2022-09-08 Bentone...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 15-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 16-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 20-2 Bentone BFG 1...
Page 39
Connect the electrical contact to the damper motor. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 18-2 Bentone BFG 1...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. 172 625 21-2 Bentone BFG 1...
Page 42
When the ignigtion transformer, air switch, gas switch and gas burner control contained in the electrical package are being replaced, no work needs to be done in the socket. When servicing/replacing components which affect the combustion, gas side leakage analysis and check should be performed on the system. Bentone BFG 1...
Required current to ensure detection Min. DC 3 µA Possible detection current Max. DC 20 µA Operational indicator lamp flashes green <5 µA DC Operational indicator lamp shines green >5 µA DC 8.8.1 Flame monitoring ionisation 172 615 02-3 Bentone...
Page 44
Max. current for flame detection Max. DC 5.5 µA Required current to ensure detection Min. DC 40 µA Possible detection current Max. DC 60 µA Operational indicator lamp flashes green <45 µA DC Operational indicator lamp shines green >45 µA DC Bentone...
Instruct the persons in charge of the operation on the service and • maintenance of the installation and what to do should any troubles occur. Inspection and service must be carried out by authorized personnel. • Review and service should be performed by authorised personnel only. 172 615 04-2 Bentone...
Voltage lower than 185V. Contact an electrician. Ignition electrodes disrupting ionisation current. Adjust ignition electrodes. Re-polarise the transformer. Poor earth connection. Ensure adequate earth connection. Phase and neutral swapped around. Check wiring diagram and change accordingly. 172 615 06 2018-01-10 Bentone...
Page 47
Flame at incorrect angle due to combustion head out of Check the combustion head and readjust. position. Condensation build up in boiler and chimney: Raise the flue gas temperature by increasing gas volume Insulate Flue gas temperature too low or gas volume too low. the chimney. Bentone...
11. Service- and inspection protocol Installation Boiler Efficiency kW: Name: Type: Address: Burner Efficiency kW: Type: Installed by: Date: Date gas/h Efficiency Governor Fluegas Ionisation Pressure temp current Fire Chimney room Measure- °C µ A ment Before After mbar mbar Small Flame Large Flame...
Page 50