BG 400-2
172 602 13 98-01

Advertisement

Table of Contents
loading

Summary of Contents for Bentone BG 500

  • Page 1 BG 400-2 172 602 13 98-01...
  • Page 2 178 001 74...
  • Page 3 DESCRIPTION COMPONENTS 1. Switch 0-I 9. Multibloc 17. Electrical connection 2. Switch I-II 10. Connecting pipe 18. Motor 3. Cover, inspection glass 11. Air damper 19. Ignition electrode 4. Reset button 12. Air intake 20. Transformer 5. Air pressure switch 13.
  • Page 4: Technical Data

    TECHNICAL DATA Type designation BG 400 DIMENSIONS Lengt of burner tube Measure A Standard Long design Town gas The above dimensions are max. measurements. Depending on the components used, the measurements may vary. OUTPUT RANGE Type Capacity Gas volume at a min Gas volume at a max Max.
  • Page 5 TECHNICAL DATA DIMENSIONS OF FLANGE ø140 172 215 30 96-01...
  • Page 6 EN 676. 5b. Gas pressure switch, maxi 6a. Main valve, 2 -stage. When mo- dulating operation is required this valve is equipped with controls for variable opening. When Bio gas is used, Bentone shall always be contacted. 172 415 05 03-01...
  • Page 7: Installation Example

    MOUNTING ON THE BOILER INSTALLATION EXAMPLE Remove the combustion unit from the REMOVAL OF FAN HOUSE UNIT burner. Fit the enclosed flange and FROM BURNER. Connect the gas to the burner by gasket to the boiler.If new fixing holes Loosen the screws. Swing out the fan means of the ball valve.
  • Page 8 ELECTRIC EQUIPMENT GAS BURNER CONTROL: LMG22.../LGB22... WIRING DIAGRAM COMPONENT LIST A1 Gas burner control B1 Ionization electrode F1 Operating fuse H1 Lamp, low capacity H2 Lamp, high capacity H3 Alarm signal 230 V M1 Burner motor M2 Damper motor, L&S SQN75.254.A21B P1 Time meter, total operating time P2 Time meter, high capacity, total opera- ting time...
  • Page 9 ELECTRIC EQUIPMENT GAS BURNER CONTROL: LMG22.../LGB22... FUNCTION 1 Operating switch ON-Thermostat ON-Gas pressure switch ON-Air damper closed. A control is made that the air pressure switch does not indicate fan pressure. Then the burner motor starts. 2 Air damper motor opens. The air damper motor opens the damper to full load.
  • Page 10 ELECTRIC EQUIPMENT CONTROL DIAGNOSIS UNDER FAULT CONDITIONS AND LOCKOUT INDICATION GAS BURNER CONTROL: LMG ... Operating concept • Burner control has initiated lockout • Reset > Red fault LED on Press lockout reset button for 0.5 ...3 s • Diagnosis of cause of fault - Wait >10 s - Press lockout reset buttonj for >3 s - Read blink code of red fault LED...
  • Page 11 MEASURES AND CHECKS BEFORE START-UP, 2-STAGE- OR MODULATING BURNERS INNER ASSEMBLY NOTE! APPLIES ONLY TO GAS LEAKAGE CONTROL Ensure that the ignition and ionisa- BURNER CONTROL LFL1. MultiBloc tion electrodes are correctly adjus- When using LPG (Propane) the bur- ted. The sketch shows the correct ner should be connected for post- measurements.
  • Page 12 MEASURES AND CHECKS BEFORE START-UP INNER ASSEMBLY Town gas INNER ASSEMBLY Natural gas, LPG Natural gas INNER ASSEMBLY Biogas (UV-detector) 172 205 78 98-01...
  • Page 13 DETERMINATION OF GAS VOLUME FOR THE INSTALLATION Specifications on natural gas, town Net calorific value gas and bio gas vary. For more exact information please contact the gas Gas quality kWh/Nm kJ/Nm kcal/Nm distributor. Natural gas 10.3 37 144 8 865 Propane 26.0 93 647...
  • Page 14: Air Adjustment

    FUNCTION, 2-STAGE DESIGN AIR ADJUSTMENT The damper motor turns the damper between three pre-set positions: fully closed, low load, full load. These positons are controlled in the motor by cams of different colours. The black cam controls the gas valve for full load. If the air volume needs changing: Remove the cover of the damper motor and change the position of the cams by turning them with the tools accompanying the burner.
  • Page 15 MULTI-BLOC, MB-ZRDLE 405-420 Max. inlet pressure: 360 mbar. 1. Ball valve Adjustable governor pressure: 2. Fixing flange 405 - 412 S50 = 4 - 50 mbar 3. Gas pressure switch 415 - 420 S20 = 4 - 20 mbar 4. Governor with pressure adjust- 415 - 420 S50 = 20 - 50 mbar ment Solenoid valve: Slow opening valves...
  • Page 16: Flow Adjustment

    ADJUSTMENT OF MULTI-BLOC, MB-ZRDLE 405-420 FLOW ADJUSTMENT ADJUSTMENT OF GOVERNOR ADJUSTMENT OF START GAS 2-STAGE DESIGN Adjust outlet pressure from governor FLOW by means of a screw driver. Min. and Remove the protective cover c. For stage 1, loosen the lock screw a. Turn the hydraulic device e: max.
  • Page 17: General Instructions

    GENERAL INSTRUCTIONS ADJUSTMENT OF BURNER SERVICE Service should only be carried out by The burner is from the factory pre-set A general rule is that the lower capa- qualified personnel. Replacement to an average value that must then be city the smaller the opening between parts should be of the same make adjusted to the boiler in question.
  • Page 18 GENERAL INSTRUCTIONS ADJUSTMENT OF BRAKE PLATE Loosen the screw on the adjust- ment device. To reduce the opening: turn the knob to the left. To increase the opening: turn the knob to the right. The adjustment of the position of the brake plate affects the air flow.
  • Page 19: General Instruction

    GENERAL INSTRUCTION ADJUSTEMNT OF MAX. GAS PRES- ADJUSTMENT OF AIR PRESSURE FLAME MONITORING AND MEASU- SURE SWITCH SWITCH REMENT OF IONISATION CURRENT The burner is equipped with a max. gas The air presure switch should stop the The burner is monitored according to pressure switch only on request.
  • Page 20 HANDING OVER OF THE INSTALLATION Make repeated start attempts to FAULT LOCATION, FUNCTIONAL ensure that the adjustments func- TROUBLES tion. Trouble free operation is dependent on three factors: electricity, gas and air Close the ball valve during opera- supply. Should there be any changes tion to check that the gas switch in the ratio between these three factors switches off at the set value.
  • Page 21 FAULT LOCATION GUIDE Gas burner The basis for trouble free operation can only be ensured To facilitate fault location we have drawn up a scheme by the correct combined effect of the three factors: showing the most frequent faults in a gas burner instal- electricity, gas flow and combustion air.
  • Page 22 CAUSE REMEDY The cable shoes have bad contact Improve the contact The ignition cables are damaged Replace The ignition transformer is damaged, no voltage on the Replace the transformer secondary side The ignition cable and the ionisation cable have been Change transposed.
  • Page 23 CAUSE REMEDY Voltage lower than 185 V Contact the electricity authorities. The ignition electrodes are disturbing the ionisation Adjust the ignition electrodes, repole the ignition transfor- current mer if necessary. Bad earthing Arrange for proper earthing. Phase and neutral transposed See wiring diagram and change.
  • Page 24 CAUSE REMEDY The ambient temperature of the gas relay is too high Heat insulate, max. 60° C. The ignition spark is too weak Check the transformer Bad combustion Bad draught conditions Check the chimney The flue gas temperature is too high The boiler is overloaded.
  • Page 25: Declaration Of Conformity

    BG 100, BG 150, BG 200, STG 120, STG 146, BG 300,BG 300LN, BG 400, BG 400LN BG 450,BG 450LN, ......................................BG 500,BG 500LN, BG 600,BG 600LN, BG 700,BG 700LN and BG 800,BG 800LN all fan gas burners ........................................to which this declaration relates is in conformity with the following standard(s) or the normative socument(s)