VRV 5 safety valve unit
4P749917-1 – 2023.09
d Extraction fan
SVS output (external alarm)
The SVS output is a potential-free contact on terminal X6M that closes in case a
leak is detected in the SV unit.
The SVS output must be used when an external alarm is required (see
determine the required safety
X6M
1 2
1 2
FAN
SVS
a
a SVS output terminals (1 and 2)
b Cable to external alarm circuit
NOTICE
The SVS output is a potential-free contact with a limited capacity of 220~240 V AC –
0.5 A.
Do NOT directly use the SVS contact in the alarm circuit. Instead, use the SVS contact
in conjunction with a power supply to energise a relay that controls the external
alarm circuit.
b
X6M
(SVS)
EXAMPLE
1
c
2
a
a SVS output terminal
b Relay power supply
c Relay
d External alarm power supply
e External alarm
Cable routing
Route the FAN or SVS output cable as indicated below. Leave ±20  cm additional
length of cable to lower the switch box.
SV1~8A