SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
a
PH2
SW8
c
b
≤ 3.2 N•m
b
a Damper wire
b Screw
c Damper
2 Connect the damper wires in the switch box:
▪ Connect the damper wire to the connector.
▪ Position the damper earth wire and tighten the damper earth wire screw.
▪ Install a cable tie to fix the connector. Make sure the wire and connector do
not touch any sharp edges.
a Connector
b Earth wire screw
c Damper earth wire
d Cable tie
3 Install the leftmost wire fixing plate. It holds the damper wire in place.
▪ Restore the insulation of the wiring fixing plate by applying the small
accessory insulation piece on top of the old, flattened insulation.
c
b
a
a Wire fixing plate
b Old flattened insulation
c New insulation (accessory)
▪ Position the wires as far down as possible in the opening on top of which the
wire fixing plate will be installed.
b
b
PH2
a
d
b
c
14
Unit installation
|
Installer and user reference guide
77