VRV 5 safety valve unit
4P749917-1 – 2023.09
Use the total amount of refrigerant in the system and the area of the room in
which the SV unit is installed to check which safety measure is required.
Note: When "No safety measure" is required, it is still allowed to apply natural
ventilation or install an external alarm or ventilated enclosure if wanted. Follow the
respective instructions as described further below.
Note: When natural ventilation is required, it is still allowed to install an external
alarm or ventilated enclosure if wanted. Follow the respective instructions as
described further below.
Note: When an external alarm is required as safety measure, it is also allowed to
install a ventilated enclosure. Follow the instructions described further below.
Use the first graph (Lowest underground floor
the lowest underground floor of a building. For other floors, use the second graph
(b)
(All other floors
).
OTHER FLOORS
LOWEST UNDERGROUND FLOOR
The graphs and table are based on an installation height of the SV unit between
1.8 m and 2.2 m. The installation height is the height of the bottom of the SV unit
to the floor. See also
"14.1.1 Installation site requirements of the
If the installation height is more than 2.2 m, different boundaries for the applicable
safety measures can apply. To know which safety measure is required in case the
installation height is more than 2.2 m, refer to the online tool
NOTICE
SV units cannot be installed lower than 1.8 m from the lowest point of the floor.
Example
The total amount of refrigerant in the VRV system is 20 kg. All SV units are installed
in spaces that do NOT belong to the lowest underground floor of the building. The
space in which the first SV unit is installed has a room area of 50 m², the space in
which the second SV unit is installed has a room area of 15 m².
Based on the graph for "All other floors" (All other floors), the room area limit is
40 m² for No safety measure" (No safety measures).
This means that the following safety measures are required:
SV unit
Room area
1
A=50 m²≥40 m²
2
A=15 m²<40 m²
13
Special requirements for R32 units
|
(a)
) in case the SV unit is installed in
Required safety measure
No safety measures
Ventilated enclosure OR
External alarm + natural ventilation
4
unit" [
 63].