Page 1
Installation and Maintenance IM 916-5 Group: Controls Part Number: IM 916 Date: August 2020 BACnet IP Communication Module for ® MicroTech III and MicroTech 4 Unit Controllers ® ® Applied Rooftop Systems and Self-Contained Units Models: DPS, DPH, MPS, RAH, RCE, RCS, RDE, RDS, RDT, RFS, RPE, RPS, SWP and SWT...
IM 916-4 Dec 2019 Rebranded layout and added MicroTech 4 Rebel Applied. Other minor corrections. to correct the interference at his or her own expense. Daikin disclaims any IM 916-5 Aug 2020 OM 1288 added to Reference Documents liability resulting from any interference or for the correction thereof.
Product Information Inc; Windows from Microsoft Corporation; Daikin, Maverick II, Rebel, and MicroTech from Daikin Applied Americas. Product Information This manual provides instructions for installing or replacing Component Data the BACnet communication module on a MicroTech 4 (Rebel Applied) or MicroTech III (Rooftop Applied Systems, Self-...
Product Information Light Emitting Diodes (LEDs) Board-to-Board Connector The BACnet communication module has a BSP LED and a The board-to-board connector connects the unit controller to BUS LED to indicate communication activity and status of the the BACnet communication module (Figure 3 Figure BACnet communication module.
Installation Installation 7. Insert the other end of the board-to-board connector Installation and Mounting to the far left side of the unit controller or other communication module, if attached (Figure The following section describes how to field install a new BACnet IP communication module or replace an existing 8.
Integration Configuring the BACnet Communication Module The following section describes how to configure the BACnet 4. Modify the parameters as necessary. See Table 3 IP communication module for BAS network integration. Follow details. these instructions to set addressing parameters for the BACnet 5.
Page 8
Integration Table 3: Network Parameter Settings Parameter Range/Default Description/Notes This name must be unique throughout the entire BACnet network. The last 6 characters of Up to 17 characters Device Object Name the default are the last 6 digits of the MAC Address, which is on a printed sticker affixed to the Default: Varies BACnet communication module.
Table 3. → Make sure there are no duplicate devices on the Contact the Daikin Applied Controls Customer Support Group network (Device Name and Device ID, for example). at 866-462-7829 for additional assistance, if necessary. → Check the use of the character # at the end of each Refer to the appropriate Unit Controller Operation Manual for IP setting.
Appendix A: BACnet IP Networks Appendix A: BACnet IP Networks BACnet IP Network Types Single IP Subnet Multiple IP Subnets In BACnet/IP networks with only IP subnet (IP domain), A BACnet/IP network may consist of multiple IP subnets broadcast messages from a device (ex. 172.16.255.255 or assigned the same BACnet network number.
Page 12
Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Need help?
Do you have a question about the BACnet MT3041 and is the answer not in the manual?
Questions and answers
Hello, I have a question: is the BAC-Net Unit MT3041 a Bacnet Server/Slave device? Best regards, Arkadij Almann
The Daikin BACnet MT3041 functions as a BACnet server device. It enables the unit controller to exchange BACnet objects with a building automation system (BAS), which is consistent with server behavior in BACnet networks.
This answer is automatically generated