The Fike logo is a trademark of Fike Corporation, registered in the U.S. and other countries. Every effort has been made to ensure that the information in this manual is accurate. However, Fike is not responsible for any inaccuracy or omission in this document. The information in this document is subject to change without notice.
Doc. No. 06-930.02 1. Introduction The FIK-IR3-H2 flame detector provides ultra-fast response, high performance and reliable detection of hydrogen fires. The detector addresses slow growing fires as well as fast eruptions of fire using improved IR3 technology. The detector operates in all weather and light conditions.
• • The field of view of the detectors Environment • Environmental conditions including but not limited to dust, snow or rain can reduce the detectors sensitivity and require additional maintenance. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Function Hex. KEY 6 mm Vertical alignment Hex. KEY 10 mm Horizontal alignment Wrench 13 mm Mounting the detector Flat Screwdriver 6 mm Ground screw connection Flat screwdriver 3.5mm Terminal connection For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
The external earthing connection consists of cable lug with M5x10 stainless steel screw, power input wiring and at a minimum of 1 • The internal terminals are suitable for connection of a wire equal to or greater than the conductor. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
0.28" (7mm) diameter holes. There are four captive screws with spring washers in the tilt mount. The following drawing shows the location of the four holes for the screws and washers. Figure 1 - Tilt Mount Base - Rear View For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
The detector is now correctly located, aligned and ready to be connected to the system. Please refer to section 0 for wiring instructions, and section 3 for a description of the detector’s configuration settings. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Figure 3 - Detector on Tilt Mount - Side View ITEM ITEM NAME TILT MOUNT ASSEMBLY HOLDING PLATE MOUNTING HEX SCREWS M8 AND LOCK WASHERS HEX SOCKET LOCKING SCREW M8 HEX SOCKET LOCKING SCREW M12 For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Table 2 - Sensitivity Levels A standard hydrogen fire is defined as a 32-in Plume of H2 fire, with maximum wind speed of 6.5 ft/s (2 m/s). For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
BIT is initiated and the “Manual BIT – Alarm Output Test” is enabled as the Manual BIT will set the 0-20mA terminal to 20mA and close the alarm relay. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
This terminal should be left connected to the housing internal ground Shield screw. RS 485 (+) RS-485 Modbus communication (used by the “Communicator” software) RS485 (-) Fault Relay (NC) Alarm Relay (NC) For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
The following drawing shows how to wire the detector to act as a current sink isolated transmitter (4- wire connection): Power Return Detector Controller Return Figure 5 - Sink 4 - Wire Scheme For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
(fault, alarm) and to initiate a BIT to each detector individually. The detector communicates via RS-485 with a Modbus RTU compatible protocol. For more details on the communication protocol, please consult with FIKE. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
FIK-IR3-H2 User Manual Doc. No. 06-930.02 Figure 8 - RS-485 Networking For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Doc. No. 06-930.02 5 Operation The FIK-IR3-H2 is a triple-IR flame detector ready for detecting fire approximately 30 seconds after power up. During this startup time the LED flashes Yellow. If the startup is successful, the indication LED turns to green, the 0-20mA indicates 4mA and the fault relay is closed.
Where dust, dirt or moisture accumulates on the window, first clean the window with a soft optical cloth and detergent, and then rinse with a clean soft cloth, cotton swab, or tissue. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Detector is exposed Check cause of alarm. • current output is at 20mA to a flame If caused by “friendly fire”, • reposition the detector so that it is not affected by it. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
• The FAULT relay will normally be energized and the contact will be closed during normal operation of the detector. The contact will be open at fault condition or low voltage. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
-67°F to + 185°F (-55°C to +85°C) • • Storage -67°F to + 185°F (-55°C to +85°C) Humidity: up to 99%, non-condensing • • Ingress Protection: IP66 & 68 (2m, 24hr); NEMA 4X & 6P For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
FIK-IR3-H2 User Manual Doc. No. 06-930.02 6.6 Label Figures 6.6.1 Ex db For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
The detector fully complies with EMC directive 2014/30/EU and protected against interference caused by RFI and EMI. The cables to the detector must be shielded and the detector must be grounded in order to comply to the EMC directive. For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...
Doc. No. 06-930.02 7 Warranty FIKE CORPORATION agrees, to the extent allowed by applicable law, to transfer and pass through to Purchaser/Distributor the following original manufacturer’s warranty from FIRE & GAS DETECTION TECHNOLOGIES INC., manufacturer and supplier of the FlameSpec products: FIRE & GAS DETECTION TECHNOLOGIES INC.
For each radiation source a distance is listed. This is the minimum tested distance, from which the detectors did not alarm when exposed to the radiation source (either modulated or non-modulated). For more information & Technical support: (800)-979-FIKE (3453) www.acornfiresecurity.com...