Fike 205-0001 Installation And Maintenance Instructions

Fike 205-0001 Installation And Maintenance Instructions

Multipoint asd detector, multipoint asd with sounder, multipoint asd with sounder / strobe

Advertisement

Quick Links

General Description
The Multipoint ASD is a plug-in type smoke detector that utilises a photo-electric sensing
chamber to make a measurement corresponding to smoke density. The device also
incorporates a thermistor sensing circuit to allow for accurate heat measurement. These
elements allow the device to be configured to a smoke, heat or combined setting. Digital
communication technology to the control panel is implemented allowing for accurate
data transfer at high transmission speeds.
Before Installation
The detector must be installed in compliance with the control panel installation manual
The installation must also meet the requirements of any local authority.
Spacing
Fike recommends spacing detectors in accordance with any local authority. Due to the effects of IR and possible
magnetic interference, detectors should not be fitted any closer than 500mm (preferably 1000mm) to a light fitting or any
other source of IR or EMI. In addition to this recommendation, the device should be mounted so that the indication LED
is facing towards the light source.
Detector Installation
All wiring must be installed in compliance with the recommendations laid out by any local authority as well as any special
recommendations documented in the control panel installation manual. The cabling used should be of a 2-core
1.5mm
screened, fire resistant type with the following characteristics:
2
Max Capacitance Core to Screen ...................................................180pF / m
Max Capacitance Core to Core ......................................................100pF / m
Max Inductance ..............................................................................1.0mH / km
Max Resistance Two Core Screened 1.5mm² ................................12.1Ω / km
It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on this
system is not permitted. Cables may be terminated into the connectors mounted in the base, as shown below. Care
should be taken when terminating devices to ensure all cables are correctly sleeved and connections are secure.
Improper connections will prevent a system from responding properly in the event of a fire.
The Loop +ve (positive) IN and the Loop +ve (positive) OUT connections are automatically
joined together (short circuit) by a spring arm between terminals 2 and 3 until the detector is
installed. This allows for cable continuity readings at the commissioning stage.
Please remember that all high voltage testing must be carried out before the installation of
the electronics, otherwise the electronics will be damaged. Please also note that the SCRN
terminal should only be connected to the loop screen and NOT the building earth.
Once all testing has been carried out on the cabling and continuity & insulation has been
proven, the Multipoint detector head may be fitted. Before installing the head remember
to note the serial number of the device (located on the rear of
the detection head) onto your drawings or configuration sheets to
enable you to prove its location later. The address allocation for
the device is carried out automatically by the control panel whilst in
initialisation mode, so addresses do not need to be set manually.
This document is only intended to be a guideline and is not applicable to all
situations. Information subject to full disclaimer at www.fike.com/disclaimer
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
205-0003 MULTIPOINT ASD DETECTOR
205-0001 MULTIPOINT ASD WITH SOUNDER
205-0012 MULTIPOINT ASD WITH SOUNDER / STROBE
*For Remote LED use Terminals
1(0v) & 3(+ve)
Terminal
Description
1 / LOOP 0V *
Loop –ve IN & OUT
2 / LOOP +IN
Loop +ve IN
3 / LOOP +OUT
Loop +ve OUT
4 / AUX +VE *
Auxiliary +ve if used
5 / AUX –VE
Auxiliary –ve if used
SCRN
Cable Screen
Document No. 26-0874 Issue 11
Subject to change
http://www.fike.co.uk/
resource-downloads/addressable/
3
4
5
2
1
N
R
C
S

Advertisement

loading
Need help?

Need help?

Do you have a question about the 205-0001 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fike 205-0001

  • Page 1 The installation must also meet the requirements of any local authority. Spacing Fike recommends spacing detectors in accordance with any local authority. Due to the effects of IR and possible magnetic interference, detectors should not be fitted any closer than 500mm (preferably 1000mm) to a light fitting or any other source of IR or EMI.
  • Page 2 Remote LED (not available if Auxiliary Input / Output used) The remote LED terminals may be used to connect a separate external LED unit (Fike part no. 600-0092) to the detector that will activate only when the device to which it is connected enters an alarm condition. The Fike LED unit incorporates the necessary 10k Ohm current limiting resistor.
  • Page 3 Replacing Multipoint ASD Detectors If a detector requires replacement after the system has been programmed and tested then proceed as follows: Stop the loop at the control panel before replacing the detector with a new one, noting its serial number onto the configuration sheets. Initialise the loop from the control panel and re-configure the loop devices using the Re-config command.
  • Page 4 Systems in and around buildings ensure that the contents of this document are correct Essential characteristics Performance at time of publication, Fike shall be under no liability Nominal activation conditions/Sensitivity, response delay (response time) whatsoever in respect of such contents. E&OE Pass...

This manual is also suitable for:

205-0003205-0012Fik-205-0012-nbFik-205-0003Fik-205-0001-nbFik-205-0001 ... Show all